APC AXFA11G user manual F14 SO1/2 Active Mode Setting of the active mode for status output

Models: AXFA11G

1 118
Download 118 pages 18.28 Kb
Page 49
Image 49
[F14: SO1/2 Active Mode] Setting of the active mode for status output

6. PARAMETER DESCRIPTION

[F12: SI1 Function] Setting of the funtion for the SI1 status input terminal This parameter sets the function for the SI1 (status input 1) terminal.

Setting

Function

Description

 

 

 

No Function

No input function

 

 

 

 

 

 

Based on the external status input, the instantaneous flow rate

 

 

indication is forcibly set to 0% (i.e., 4 mA), and both totalization

0% Signal Lock

0% signal lock via external status

and pulse outputs are halted. This setting has precedence over

input.

the output signal whenever an alarm occurs. When 0% signal lock

 

 

 

is canceled, the instantaneous flow rate is restored in accordance

 

 

with the time constant originally set using B20/C11:Flow Damping.

 

 

 

 

Automatic zero adjustment via

Automatic zero adjustment is carried out in response to

Ext Auto Zero

external status input. For more details regarding automatic

external status input

 

zero adjustment, refer to Chapter 9: Operation.

 

 

 

 

 

Ext Ttl Preset

Forward totalization preset via

The totalization display value is preset or reset to zero in

accordance with the external status input. The preset value is

external status input

 

determined using D21: Ttl Set Val Lower and D22: Ttl Set

 

 

 

Reverse totalization preset via

Val Upper.

Ext Rev Ttl Set

In case that “Start” is selected for D20: Total Execution , the

external status input

 

count for totalization starts from the preset value.

 

 

 

Ext 2 Ranges

2 ranges switching via external

 

status input

 

 

 

Ext 3 Ranges

3 ranges switching via external

This function allows switching of up to 4 ranges in

status input (Note 1)

response to status input for a single direction only.

 

Ext 4 Ranges

4 ranges switching via external

 

status input (Note 1)

 

 

 

 

 

 

Note 1: When these functions are selected, two terminals become necessary for status input.

Accordingly, the setting for F12: SI1 Function is automatically adopted as the setting for F13: SI2 Function.

(Setting of these functions is not possible using F13: SI2 Function.)

Note 2: Function-specific SI1 and SI2 operations

Operations are performed in accordance with the content of the following table when the active mode has been set to "Short Active" using F15: SI1/2 Active Mode.

Operating patterns are reversed when the active mode has been set to "Open Active" using this parameter.

T0625.EPS

Selected function

Condition of SI1 or SI2

 

 

Open

Short

 

 

 

 

0% Signal Lock

Normal

Signal lock status

 

 

 

Ext Auto Zero

Normal

Start of automatic zero adjustment

 

 

 

Ext Ttl Preset

Normal

Forward totalization preset

 

 

 

Ext Rev Ttl Set

Normal

Reverse totalization preset

 

 

 

Note: For “Ext 2 Ranges,” “Ext 3 Ranges,” and “Ext 4 Ranges,” see the Multiple

ranges setting section.

T0626.EPS

[F13: SI2 Function] Setting of the function for the SI2 status input terminal

This parameter sets the function for the SI2 (status input 2) terminal. Selectable functions are the same as for F12: SI1 Function; however, the selection of Ext 3 Ranges and Ext 4 Ranges is not possible for F13.

[F14: SO1/2 Active Mode] Setting of the active mode for status output

This parameter sets the active mode for the terminals SO1 and SO2. Active modes cannot be set individually for these two terminals.

Setting

Function

 

 

Closed (On) Act

Status output becomes "Closed (On)" when an

 

event occurs.

Open (Off) Act

Status output becomes "Open (Off)" when an

event occurs.

 

 

 

 

T0627.EPS

Example: When the “Total Switch” function is selected for SO1 or SO2

Closed(On)

Open(Off)

Equal or above setting value Equal or above setting value

Closed (On) Active

Open (Off) Active

 

F0605.EPS

6-21

IM 01E20C01-01E

Page 49
Image 49
APC AXFA11G user manual F14 SO1/2 Active Mode Setting of the active mode for status output