8. OPERATION VIA HART COMMUNICATOR

Open the “Auto Poll” display:

5. HART Output Online Menu Main Menu

F3 : HOME

4.Utility 1. Configure Communication

1. Polling

1AXFA11 : FI-1201

HART Output

 

 

1

Poll addr

1

2

Num req preams

5

3

Burst

mode

On

4

Burst

option

PV

HELP SAVE HOME

2AXFA11 : FI-1201 Online

1

Device Setup

 

2

PV

20m3/h

3

PV AO1

20mA

4

PV Span

20m3/h

SAVE

3HART Communicator 1 Offline

2 Online

3 Frequency Device

4 Utility

4HART Communicator Utility

1 Configure Communic

2 System Information

3 Listen for PC

4 Storage Location

5 Simulation

F3

(HOME)

JLK

4

STU or 1

Return to the “Online” menu with HOME (F3).

Return to the “Main” menu with a “previous” key.

Select “Utility”.

Select “Configure Communication”.

5

6

HART Communicator Configure Communica

1Polling

2Contrast

3Off Time

4Ignore diagnostics

5Delete Configs

HELP

HART Communicator

Polling

Never Poll

Never Poll

Ask Before Polling

Always Poll

Digital Poll

HELP

 

 

 

ESC

 

ENTER

STU or 1

3

F4

(ENTER)

Select “Polling”.

Select “Digital Poll” and press ENTER (F4).

F0819.EPS

NOTE

1.If “Never Poll” is selected in “Polling” when the address is assigned, the “Online Menu” cannot be called up and displayed. Be sure to select “Digital Poll” in “Polling” after assigned the polling address.

2.When the same polling address is assigned for two or more field devices in multidrop mode, communication with these field devices is disabled.

8-16

IM 01E20C01-01E

Page 90
Image 90
APC AXFA11G user manual Polling