6. PARAMETER DESCRIPTION

 

 

 

 

 

 

 

 

 

 

Name

 

Data range

 

Position

Default value

 

 

Item

 

 

 

Units

Description

 

Display unit

R/W

Display unit

of decimal

 

(*): Indicated item

 

 

 

 

(BRAIN)

 

/BRAIN

 

point

 

 

 

 

 

 

 

 

 

 

 

 

B22

Base Time Unit

W

/d

 

 

/s (*)

Selects time units for the flow

 

 

(TIME UNIT)

 

/h

 

 

 

rate span. Linked with C41.

 

 

 

 

/min

 

 

 

 

 

 

 

 

/s

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B23

Flow Span

W

0.0001 to 32000

B21

0 to 4

1 m/s (*)

Sets flow rate span (with units

 

 

(FLOW SPAN)

 

 

/B22

 

 

from B21 and B22). Linked with

 

 

 

 

 

(C40/C41)

 

 

C42.

 

B24

Flow Decimal Pnt

W

Auto

 

 

Auto (*)

Selects decimal point position

 

 

(FLOW DECIMAL)

 

0

 

 

 

for the display unit's

 

 

 

 

1

 

 

 

instantaneous flow rate. Linked

 

 

 

 

2

 

 

 

with C43.

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B30

Total Unit

W

n Unit/P

 

 

Pulse/s (*)

Selects the flow rate unit per one

 

 

(TOTAL UNIT)

 

u Unit/P

 

 

 

pulse as used for totalization

 

 

 

 

m Unit/P

 

 

 

display. Linked with D10.

 

 

 

 

Unit/P

 

 

 

 

 

 

 

 

k Unit/P

 

 

 

 

 

 

 

 

M Unit/P

 

 

 

 

 

 

 

 

Pulse/s

 

 

 

 

 

B31

Total Scale

W

0 to 32000

B30

0 to 4

0 (*)

Sets the flow rate per one pulse

 

 

(TOTAL SCALE)

 

 

(D10)

 

 

for the totalization display.

 

 

 

 

 

 

 

 

Linked with D11.

 

B32

Pulse Unit

W

n Unit/P

 

 

Pulse/s (*)

Selects the flow rate unit per one

 

 

(PULSE UNIT)

 

u Unit/P

 

 

 

pulse as used for pulse output.

 

 

 

 

m Unit/P

 

 

 

Linked with E10.

 

 

 

 

Unit/P

 

 

 

 

 

 

 

 

k Unit/P

 

 

 

 

 

 

 

 

M Unit/P

 

 

 

 

 

 

 

 

Pulse/s

 

 

 

 

 

B33

Pulse Scale

W

0 to 32000

B32

0 to 4

0 (*)

Sets the flow rate per one pulse

 

 

(PULSE SCALE)

 

 

(E10)

 

 

as used for pulse output.

 

 

 

 

 

 

 

 

Linked with E11.

 

B40

Display Select1

W

Flow Rate(%)

 

 

Flow Rate

Selects content of the first line

 

 

(DISP SELECT1)

 

Flow Rate

 

 

 

for Display Mode. Linked with

 

 

 

 

Flow Rate(mA)

 

 

 

H10.

 

 

 

 

Forward Total

 

 

 

 

 

 

 

 

Reverse Total

 

 

 

 

 

 

 

 

Dif Total

 

 

 

 

 

B41

Display Select2

W

Off

 

 

Off

Selects content of the second line

 

 

(DISP SELECT2)

 

Flow Rate(%)

 

 

 

for Display Mode. Linked with

 

 

 

 

Flow Rate

 

 

 

H11.

 

 

 

 

Flow Rate(mA)

 

 

 

 

 

 

 

 

Flow Rate(Bar)

 

 

 

 

 

 

 

 

Forward Total

 

 

 

 

 

 

 

 

Reverse Total

 

 

 

 

 

 

 

 

Dif Total

 

 

 

 

 

 

 

 

Tag No

 

 

 

 

 

 

 

 

Adhesion Check

 

 

 

 

 

 

 

 

Communication

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B42

Display Select3

W

ame as B41

 

 

Off

Selects content of the third line

 

 

(DISP SELECT3)

 

(Display Select2)

 

 

 

for Display Mode. Linked with

 

 

 

 

 

 

 

 

H12.

 

B50

Auto Zero Exe

W

No Execution

 

 

No Execution

Selects whether or not automatic

 

 

(AUTOZERO EXE)

 

Execution

 

 

 

zero adjustment is carried out.

 

 

 

 

 

 

 

 

Linked with M10.

 

 

 

 

 

 

 

 

 

 

B60

R

Good

 

 

 

See “6.5 Alarm Functions”.

 

 

(SELF CHECK)

 

Error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T0603-2.EPS

6-3

IM 01E20C01-01E