4.4.5Grounding
CAUTION
Be sure to connect the protective grounding of the AXFA11 with a cable of 2mm2 or larger cross section in oder to avoid electrical shock to the operators and maintenance engineers and to prevent the influence of external noise. Connect the grounding wire to the mark (100 or less).
IMPORTANT
When optional code A (lighting protector) is selected, the ground should satisfy Class C requirements (grounding resistance, 10 or less).
•The protective grounding terminals are located on the inside and outside of the terminal area.
Either terminal may be used.
•Use 600 V vinyl insulation wires as the grounding wires.
Protective grounding terminals | F0414.EPS |
|
Figure 4.4.4 Protective Grounding Terminal Location
4. WIRING
4.4.6Wiring the Remote Flowtube with the AXFA11 Converter
WARNING
Before wiring, be sure that the power supply for AXFA11 converter has been turned off to prevent an electrical shock.
(1)Connection with the Remote Flowtube
Connect wiring as shown in the figure below.
I+ | I– | SO1+ SO2+ | COM | AL+ | AL– | C | SA | A | B | SB |
CURRENT OUT | STATUS OUT | ALARM OUT |
|
| SIGNAL |
|
| |||
|
|
|
|
|
|
|
|
|
| AXFA11 Converter |
N/– | L/+ |
| P+ | P– | SI1+ |
| SI2+ | COM |
|
|
POWER SUPPLY |
| PULSE OUT |
| STATUS IN |
|
|
|
AXFC Dedicated signal cable
Excitation cable
|
| Converter | Remote | |
|
| flowtube | ||
|
|
| ||
|
| SA | Taping* | |
|
| A | A | |
|
| B | B | |
|
| SB | Taping* | |
A | EX2 | C | C | |
EX1 | EX1 | |||
| ||||
B |
| EX2 | EX2 | |
| * Individually tape and insulate the | |||
|
| |||
|
| shields corresponding to SA and | ||
| EX1 | SB on the remote flowtube side. | ||
|
|
| ||
| C |
|
| |
| Remote flowtube |
| F0415.EPS | |
|
|
|
Figure 4.4.5 Wiring Diagram
(2)Connection with the Remote Flowtube (Explosion proof Type, Size 2.5 to 400 mm (0.1 to 16 in.))
IMPORTANT
In case of TIIS Flame proof type, a remote flowtube cannot be combined with AXFA11 converter. In this case, use the AXFA14 con- verter.
IM |