7. OPERATION VIA BRAIN TERMINAL (BT200)

7.3.2BT200 Setting of Numeric-Type Data: Flow rate span

In this example, the flow rate span specified by the numeric-type parameter B23: Flow Span is changed from

100.000 l/min. to 120.000 l/m.

 

 

 

 

 

 

 

 

 

 

 

When Menu Screen (Major

 

 

MENU

 

 

 

 

 

 

A:DISPLAY

 

 

 

 

Item Parameter Search

 

 

B:EASY SETUP

 

 

 

 

 

 

 

 

 

Mode) has been entered as

 

 

C:BASIC SETUP

 

 

 

 

shown here, press the

 

 

D:TOTAL SET

 

 

 

 

 

 

 

 

 

 

 

 

 

E:PULSE SET

 

 

 

 

key to move to

 

 

F:STATUS FUNC

 

 

 

 

B: EASY SETUP.

 

 

 

 

 

 

 

 

 

 

 

 

 

HOME

 

SET

 

ADJ

 

ESC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

When the cursor has been

 

 

MENU

 

 

 

 

 

 

A:DISPLAY

 

 

 

 

moved to B: EASY SETUP.

 

 

B:EASY SETUP

 

 

 

 

Press the

key to

 

 

C:BASIC SETUP

 

 

 

 

 

 

D:TOTAL SET

 

 

 

 

access Parameter Screen

 

 

E:PULSE SET

 

 

 

 

 

 

 

 

 

 

(Sub-Item Parameter

 

 

 

F:STATUS FUNC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Search Mode).

 

 

 

HOME

 

SET

 

ADJ

 

ESC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SETTING

 

 

 

 

 

 

In this example, the value

 

 

B23:FLOW SPAN

 

 

 

 

100.000l/min

 

“120” is entered, press the

 

 

+

 

 

120

 

 

 

key.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DEL

 

CLR

ESC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The data will begin to flash

 

 

SETTING

 

 

 

B23:FLOW SPAN

 

on and off: Press the

 

 

 

 

100.000l/min

 

 

 

key once again

 

 

 

+

120

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PRINTER OFF

 

to confirm your entry.

 

 

 

In case of cancel, press the

 

 

F2:PRINTER ON

 

 

 

 

(

 

) key.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

FEED

 

POFF

 

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

PARAMETER

B10:LANGUAGE

English B20:FLOW DAMPING

3.0s

B21:FLOW UNIT l(Liter)

DATA DIAG PRNT ESC

In the parameter list, the parameter for setting of flow rate span is B23: FLOW

SPAN. Press the

key four times to move the cousor to B23.

(Note that the key

can be used to move the cursor to the top of the next screen.

SETTING B23:FLOW SPAN

120.000l/min

FEED

 

 

 

NO

 

OK

The value for flow span has been changed to “120.000 l/min.”

Press ( OK ) key to exit Setting Screen

(Parameter Replacement Mode), and then the display returns to Parameter Screen (Sub-Item Parameter Search Mode) of Menu B items.

In case of redo of setting,

or

PARAMETER

After moving the cursor to

B22:TIME UNIT

B23: FLOW SPAN, press

/min

the

key to access

B23:FLOW SPAN

100.000l/min

Setting Screen (Parameter

B24:FLOW DECIMAL

Replacement Mode).

l

press the

(

NO

) key

to return the Setting Screen (Parameter Replacement Mode).

( OK )

DATA DIAG PRNT ESC

SETTING

In this mode, new values can

B23:FLOW SPAN

be entered into the

100.000l/min

highlighted field using the

 

PARAMETER B22:TIME UNIT

/min B23:FLOW SPAN

120.000l/min B24:FLOW DECIMAL

l

DATA DIAG PRNT ESC

The changed setting for flow rate span can now be confirmed.

Press the

(

ESC

) key

to return to Menu Screen (Major Item Parameter Search Mode).

+

0

 

alphanumeric keys.

F0708.EPS

DEL CLR ESC

7-6

IM 01E20C01-01E

Page 73
Image 73
APC AXFA11G user manual 2 BT200 Setting of Numeric-Type Data Flow rate span, B23 Flow SPAN, press