APC AXFA11G N11 Test Output Value Setting for test output, Menu P Parameter Protection items

Models: AXFA11G

1 118
Download 118 pages 18.28 Kb
Page 62
Image 62
[N11: Test Output Value] Setting for test output

(3)“Normal” will be restored when the power is turned off or when 30 minutes have elapsed since entry to Test Mode.

(4)In Test Mode, the warning 83: Fix Cur Wng will be displayed as a warning message. (For more details, refer to Section 6.5 Alarm Functions.)

[N11: Test Output Value] Setting for test output

values

During loop testing, current output (4 to 20mA), totalization, and pulse will be output in accordance with this parameter’s setting, and values can be set when “Test” has been selected for N10: Test Mode. With multiple ranges or when performing forward/ reverse flow measurements, setting should be done using a percentage of the maximum range.

[N20: Test SO1] Setting for SO1 output terminal condition during testing

This parameter sets the condition of the SO1 status output terminal during loop testing. Setting is possible when “Test” has been selected for N10: Test Mode.

Setting

Function

 

 

Open (Off)

SO1 output terminal in Open (Off) condition

 

 

Closed (On)

SO1 output terminal in Closed (On) condition

 

 

 

T0645.EPS

[N21: Test SO2] Setting for SO2 output terminal condition during testing

This parameter sets the condition of the SO2 status output terminal during loop testing. Setting is possible when “Test” has been selected for N10: Test Mode.

Setting

Function

Open (Off)

SO2 output terminal in Open (Off) condition

 

 

Closed (On)

SO2 output terminal in Closed (On) condition

 

 

 

T0645-2.EPS

[N22: Test Alarm Out] Setting for alarm terminal condition during testing

This parameter sets the condition of the alarm output terminal (AL) during loop testing.

Setting

Function

Open (Off)

AL output terminal in Open (Off) condition

 

 

Closed (On)

AL output terminal in Closed (On) condition

 

 

 

T0645-3.EPS

[N23: Test SI1] Display for SI1 status input terminal condition during testing

This parameter is used to display the condition of the SI1 status input terminal during loop testing.

 

6. PARAMETER DESCRIPTION

 

 

 

Setting

Function

 

Open

SI1 input terminal in Open condition

 

 

 

 

Short

SI1 input terminal in Short condition

 

 

 

 

 

T0646.EPS

[N24: Test SI2] Display for SI2 status input terminal condition during testing

This parameter is used to display the condition of the SI2 status input terminal during testing.

Setting

Function

 

 

Open

SI2 input terminal in Open condition

 

 

Short

SI2 input terminal in Short condition

 

 

 

T0646-2.EPS

(12) Menu P: Parameter Protection items

Menu P contains items that are relevant to write protection and passwords.

[P10: Key Code] Parameter of the display restriction This parameter restricts access to the Service Mode.

NOTE

Write Protect function

￿The parameters P20 through P23 are set when using the write protect function. Specifi- cally, this function responds to a hardware switch or the setting of a software password, and it protects parameters from being over- written.

￿If the hardware switch is set to “Protect”, it will not be possible to overwrite parameters; furthermore, this condition will be maintained until the switch is set to “Enable”.

￿For more details regarding hardware switch settings, refer to Section 10.2.2: Setting of Write Protect Switch.

[P20: Write Protect] Status indication for write protection

This parameter is used to indicate whether or not write protection is currently on.

Default setting (Enable)

P20:Write Protect

No

F0620.EPS

Write protection (Protect)

P20:Write Protect

Yes

F0621.EPS

6-34

IM 01E20C01-01E

Page 62
Image 62
APC AXFA11G N11 Test Output Value Setting for test output, Menu P Parameter Protection items, Write Protect function