P1 - 46▲

 

 

Chapter 7 Servo ParametersASDA-AB Series

 

 

 

 

 

GR3

Encoder Output Pulse Number

 

Communication Addr.: 012EH

 

 

 

 

 

 

Default: 1

 

 

Related Section: N/A

Applicable Control Mode: ALL

Unit: Pulse

Range: 10020 ~ 12500

Settings:

This parameter is used to set the pulse number of encoder outputs which directly represents the encoder output pulse number per motor revolution.

A

B

A: Range of the pulse numbers of encoder outputs

Range of the setting value: 20 ~ 2500 (with B=1)

B: Must be set to 1

When B=1, the setting value A directly represents the pulse numbers of encoder outputs per motor revolution. At this time, the range of the setting value A is 20 ~ 2500.

The Default: indicates that the pulses will be output from the encoder directly. If

the users want to set the pulse numbers of encoder outputs, ensure to set the setting value B to

“1”. If the setting value B is not set to “1”, LCD display will show , which indicates

that the setting value is error or invalid.

For example:

If P1-46 is set to 11250, it indicates that the encoder output pulse number is 1250 pulses per motor revolution.

If P1-46 is set to 10500, it indicates that the encoder output pulse number is 500 pulses per motor revolution.

Revision January 2009

7-45