Chapter 12 Application Examples ASDA-AB Series

12.7 Internal Auto Running Mode

„Relevant Parameters Description

Parameter

Communication

Parameter Description

Address

 

 

P1-01

0101H

Control Mode and Output Direction

 

 

001: Forward torque in Pr mode

 

 

101: Reverse torque in Pr mode

 

 

 

P1-33

0121H

Position Control Mode (Pr)

 

 

5: Continuous auto-running position command (Absolute)

 

 

6: Continuous auto position command (Incremental)

 

 

 

P1-34

0122H

Acceleration Time

 

 

1st to 3rd step Acceleration time (When parameter P1-36 is set to 0,

 

 

accel / decel function is disabled, i.e. P1-34, P1-35 is disabled)

P1-35

0123H

Deceleration Time

 

 

1st to 3rd step Deceleration time (When parameter P1-36 is set to 0,

 

 

accel / decel function is disabled, i.e. P1-34, P1-35 is disabled)

P1-36

0124H

Accel /Decel S-curve

 

 

When parameter P1-36 is set to 0, accel / decel function is disabled,

 

 

i.e. P1-34, P1-35 is disabled.

 

 

 

P1-44

012CH

Electronic Gear Ratio (1st Numerator) (N1)

 

 

If the electronic gear deceleration ratio is 1/75, set numerator to 75

 

 

 

P1-45

012DH

Electronic Gear Ratio (Denominator)

 

 

 

P1-47

012FH

Homing Mode

 

 

202: When (MD1, MD0)=(OFF, ON), Forward Homing

 

 

203: When (MD1, MD0)=(OFF, ON), Reverse Homing

 

 

 

P1-50

0132H

Homing Offset Rotation Number

 

 

 

P1-51

0133H

Homing Offset Pulse Number

 

 

Total homing offset pulse number =P1-50 x 10000 + P1-51

 

 

 

P2-44

022CH

Digital Output Mode Setting

 

 

0: General output mode

 

 

1: Combination output mode

 

 

 

P2-45

022DH

Combination Output Signal Delay Time [UNIT: 4msec]

 

 

Output signal will hold delay time when position command is

 

 

completed.

P2-51

0233H

Internal Servo ON setting

 

 

 

Revision January 2009

12-25

Page 322
Image 322
Delta Electronics ASDA-AB manual Internal Auto Running Mode, „ Relevant Parameters Description