Chapter 6 Control Modes of OperationASDA-AB Series

6.3Speed Control Mode

The speed control mode (S or Sz) is usually used on the applications of precision speed control, such as CNC machine, etc. ASDA-AB series servo drive supports two kinds of command sources in speed control mode. One is external analog signal and the other is internal parameter. The external analog signal is from external voltage input and it can control the speed of servo motor. There are two usage of internal parameter, one is set different speed command in three speed control parameters before operation and then using SPD0 and SPD1 of CN1 DI signal perform switching. The other usage is using serial communication to change the setting value of parameter.

Beside, in order to make the speed command switch more smoothly, ASDA-AB series servo drive also provides complete S-curve profile for speed control mode. For the closed-loop speed control, ASDA-AB series servo drive provides gain adjustment function and an integrated PI or PDFF controller. Besides, two modes of tuning technology (Manual/Auto) are also provided for the users to select (parameter P2-32).

There are two turning modes for gain adjustment: Manual and Auto modes.

„Manual Mode: User-defined loop gain adjustment. When using this mode, all auto and auxiliary function will be disabled.

„Auto Mode: Continuous adjustment of loop gains according to measured inertia, with ten levels of system bandwidth. The parameter set by user is default value.

6.3.1 Command Source of Speed Control Mode

Speed command Sources:

1)External analog signal: External analog voltage input, -10V to +10V

2)Internal parameter: P1-09 to P1-11

Speed

CN1 DI signal

 

 

 

 

 

 

Command Source

Content

 

Range

Command

SPD1

SPD0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S

External

Voltage between V-

 

+/-10 V

 

 

 

 

analog signal

REF-GND

 

S1

0

0

Mode

 

 

 

Sz

N/A

Speed command is

 

0

 

 

 

 

 

 

 

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

S2

0

1

 

 

 

P1-09

 

0~5000r/min

 

 

 

Internal parameter

 

 

 

S3

1

0

P1-10

 

0~5000r/min

 

 

 

 

 

 

 

 

 

S4

1

1

 

 

 

P1-11

 

0~5000r/min

 

 

 

 

 

 

 

 

 

„State of SPD0~1: 0: indicates OFF (Normally Open); 1: indicates ON (Normally Closed)

„When SPD0 and SPD1 are both = 0 (OFF), if the control mode of operation is Sz, then the speed command is 0. Therefore, if the users do not use analog voltage as speed command, the users can choose Sz mode and avoid the zero point drift problem of analog voltage signal. If the speed control mode is S mode, then the command is the analog voltage between V-REF and

Revision January 2009

6-13

Page 116
Image 116
Delta Electronics ASDA-AB manual Command Source of Speed Control Mode, Ref-Gnd