Delta Electronics ASDA-AB manual Tlmod, Torque Limit Mixed Mode Communication Addr H

Models: ASDA-AB

1 357
Download 357 pages 17.54 Kb
Page 223
Image 223

Chapter 7 Servo ParametersASDA-AB Series

P2 - 64

TLMOD

Torque Limit Mixed Mode

 

Communication Addr.: 0240H

 

 

 

 

Default: 0

 

Related Section: N/A

Applicable Control Mode: Pt, Pr, S

 

 

Unit: N/A

 

 

Range: 0 ~ 3

 

 

Settings:

 

 

 

 

PL: Positive Limit

 

 

NL: Negative Limit

 

 

Tref: Torque Analog Input Voltage

 

 

Tpl: Actual PL value in “Torque Limit Mixed Mode”

 

 

Tnl: Actual NL value in “Torque Limit Mixed Mode”

0:Disabled

1:Torque limit mixed mode (No polarity) If Tref<PL, Tpl = Tref

If Tref>PL, Tpl = PL

If Tref<NL, Tnl = Tref If Tref>NL, Tnl = NL

2:Torque limit mixed mode (Positive)

If 0<Tref<PL, Tpl = Tref

If Tref>PL, Tpl = PL

If Tref<0, Tpl,Tnl = 0

3:Torque limit mixed mode (Negative) If Tref>0, Tpl,Tnl = 0

If -NL<Tref<0, Tnl = -Tref If Tref<-NL, Tnl = NL

This parameter can allow the users to set two different kinds of torque limit command sources when limiting torque. We call it is “Torque Limit Mixed Mode”.

The torque limit function is activated by parameter P1-02 or via digital input TRQLM, TLLM or TRLM.

If the users use TRQLM or P1-02 to activate torque limit function, the torque limit command source can be analog input or internal parameters (P1-12 to P1-14) depending on which way you use to activate torque limit function. At this time, the limit of PL and NL in the figure below are specified as the torque limit that determined by the torque limit command source.

If the users use TLLM or TRLM to activate torque limit function, the torque limit command source can be parameter P1-12 (NL) or P1-13 (PL).

7-74

Revision January 2009

Page 223
Image 223
Delta Electronics ASDA-AB manual Tlmod, Torque Limit Mixed Mode Communication Addr H