Chapter 12 Application ExamplesASDA-AB Series

DO Signal

Parameter Setting

Explanation

DO1

P2-18 = 101

 

 

 

 

DO2

P2-19 = 103

Please refer to “Definition of DO Signals” in the

 

 

DO3

P2-20 = 109

following section.

 

 

DO4

P2-21 = 105

 

 

 

 

DO5

P2-22 = 107

 

 

 

 

NOTE

1) Please set parameter P2-08 to 12 before changing the setting value of DI and DO signals.

„Mode Functions

MDP0, MDP1

Status

MD1

MD0

Explanation

 

1

OFF

OFF

Torque decrease

 

 

 

 

 

OFF

2

OFF

ON

Feed step position mode

 

 

 

 

3

ON

OFF

Homing mode

 

 

 

 

 

 

 

4

ON

ON

Emergency stop

 

 

 

 

 

 

-

-

-

Don’t care

 

 

 

 

 

ON

-

OFF

ON

CW manual operation

 

 

 

 

-

ON

OFF

CCW manual operation

 

 

 

 

 

 

 

-

-

-

Don’t care

 

 

 

 

 

NOTE

1)The emergency stop warning message will appear if MD0 and MD1 are ON after power suppliers to AC servo drive. If turn MD0 and MD1 to be OFF, the emergency stop warning message will disappear automatically.

2)When the status is switched from 2 (MD1=OFF, MD0=ON) to 3 (MD1=ON, MD0=OFF), the emergency stop warning message will appear. On the other hand, the emergency stop warning message will also appear when the status is switched from 3 to 2. Therefore, no matter what status you want to switch to, it is needed to switch to status 1 first to perform torque decrease (for example, switch from 2 Æ 1Æ 3 or 3 Æ 1 Æ 2).

3)Ensure that MD0 and MD1 are set to ON state to enforce an emergency stop.

12-16

Revision January 2009

Page 313
Image 313
Delta Electronics ASDA-AB manual „ Mode Functions, MDP0, MDP1