Chapter 6 Control Modes of OperationASDA-AB Series

Position

POS2

POS1

POS0

CTRG

Parameters

Description

Command

 

 

 

 

 

 

 

P5

1

0

0

 

 

P1-23

Rotation number (+/- 30000)

 

 

 

 

 

 

 

 

P1-24

Pulses (+/- max cnt)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P6

1

0

1

 

 

P1-25

Rotation number (+/- 30000)

 

 

 

 

 

 

 

 

P1-26

Pulses (+/- max cnt)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P7

1

1

0

 

 

P1-27

Rotation number (+/- 30000)

 

 

 

 

 

 

 

 

P1-28

Pulses (+/- max cnt)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P8

1

1

1

 

 

P1-29

Rotation number (+/- 30000)

 

 

 

 

 

 

 

 

P1-30

Pulses (+/- max cnt)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

State of POS0~2: 0 indicates the contact is OFF (Normally Open)

CTRG

1 indicates the contact is ON (Normally Closed)

: the instant time when the contact changes from 0 (open) to 1 (closed).

The application of absolute and incremental position control is various and multiple. This kind of position control is equal to a simple sequence control. User can easily complete the cycle running by using the above table. For example, the position command, P1 is 10 running and P2 is 20 running. Give the position command P1 first and then give the position command P2. The difference between absolute and incremental position control is shown as the figure below:

Absolute Type

10 turns

Incremental Type

20 turns

20 turns

10 turns

6.2.3 Structure of Position Control Mode

Basic Structure:

6-4

Revision January 2009