PrefaceASDA-AB Series

Wiring

¾Connect the ground terminals to a class-3 ground (Ground resistance should not exceed 100 Ω). Improper grounding may result

in electric shock or fire.

¾Do not connect any power supplies to the U, V, W terminals. Failure to observe this precaution may result in serious injury, damage to the drive or fire.

¾Ensure that all screws, connectors and wire terminations are secure on the power supply, servo drive and motor. Failure to observe this caution may result in damage, fire or personal injury.

Operation

¾Before starting the operation with a mechanical system connected, change the drive parameters to match the user-defined

parameters of the mechanical system. Starting the operation without matching the correct parameters may result in servo drive or motor damage, or damage to the mechanical system.

¾Ensure that the emergency stop equipment or device is connected and working correctly before operating the motor that is connected to a mechanical system.

¾Do not approach or touch any rotating parts (e.g. shaft) while the motor is running. Failure to observe this precaution may

cause serious personal injury.

¾In order to prevent accidents, the initial trial run for servo motor should be conducted under no load conditions (separate the

motor from its couplings and belts).

¾For the initial trial run, do not operate the servo motor while it is connected to its mechanical system. Connecting the motor to its mechanical system may cause damage or result in personal injury during the trail run. Connect the servo motor once it has successfully completed a trail run.

¾Caution: Please perform trial run without load first and then perform trial run with load connected. After the servo motor is running normally and regularly without load, then run servo motor with load connected. Ensure to perform trial run in this order to prevent unnecessary danger.

¾Do not touch either the drive heat sink or the motor during operation as they may become hot and personal injury may result.

Maintenance and Inspection

¾Do not touch any internal or exposed parts of servo drive and servo motor as electrical shock may result.

¾Do not remove the operation panel while the drive is connected to an electrical power source otherwise electrical shock may result.

¾Wait at least 10 minutes after power has been removed before touching any drive or motor terminals or performing any wiring and/or inspection as an electrical charge may still remain in the servo drive and servo motor with hazardous voltages even after power has been removed.

¾Do not disassemble the servo drive or motor as electric shock may result.

¾Do not connect or disconnect wires or connectors while power is applied to the drive and motor.

¾Only qualified personnel who have electrical knowledge should conduct maintenance and inspection.

Main Circuit Wiring

¾Install the encoder cables in a separate conduit from the motor power cables to avoid signal noise. Separate the conduits by

30cm (11.8inches) or more.

¾Use multi-stranded twisted-pair wires or multi-core shielded-pair wires for signal, encoder (PG) feedback cables. The maximum length of command input cable is 3m (9.84ft.) and the maximum length of encoder (PG) feedback cables is 20m (65.62ft.).

¾As a charge may still remain in the drive with hazardous voltages even after power has been removed, be sure to wait at least 10 minutes after power has been removed before performing any wiring and/or inspection.

¾It is not recommended to frequently power the drive on and off. Do not turn the drive off and on more than once per minute as

high charging currents within the internal capacitors may cause damage.

Main Circuit Terminal Wiring

¾Please perform the wiring after the terminal blocks are all removed from the drive.

¾ Insert only one wire into one terminal on the terminal block.

¾ When inserting wires, please ensure that the conductors are not shorted to adjacent terminals or wires.

¾Ensure to double check the wiring before applying power to the drive.

¾If the wiring is in error, perform the wiring again with proper tools. Never use force to remove the terminals or wires. Otherwise, it may result in malfunction or damage.

Revision January 2009

iii

Page 4
Image 4
Delta Electronics ASDA-AB Operation, Maintenance and Inspection, Main Circuit Wiring, Main Circuit Terminal Wiring