P1 - 56

 

 

Chapter 7 Servo ParametersASDA-AB Series

 

 

 

 

 

OVW

Output Overload Warning Level

 

Communication Addr.: 0138H

 

 

 

 

 

 

Default: 120

 

Related Section: N/A

Applicable Control Mode: ALL

 

 

 

Unit: %

 

 

 

 

Range: 0 ~ 120

Settings:

This parameter is used to set output overload level. When the motor has reached the output overload level set by parameter P1-56, the motor will send a warning to the drive. After the drive has detected the warning, the DO signal OLW will be activated.

tOL = Permissible Time for Overload x the setting value of parameter P1-56

When overload accumulated time (continuously overload time) exceeds the value of tOL, the overload warning signal will output, i.e. DO signal, OLW will be ON. However, if the overload accumulated time (continuously overload time) exceeds the permissible time for overload, the overload alarm (ALE06) will occur.

For example:

If the setting value of parameter P1-56 (Output Overload Warning Level) is 60%, when the permissible time for overload exceeds 8 seconds at 200% rated output, the overload fault (ALE06) will be detected and shown on the LED display.

At this time, tOL = 8 x 60% = 4.8 seconds

Result:

P1 - 57

P1 - 58

P1 - 59

P1 - 60

P1 - 61

When the drive output is at 200% rated output and the drive is continuously overloaded for 4.8 seconds, and the overload warning signal will be ON (DO code is 10, i.e. DO signal OVW will be activated). If the drive is continuously overloaded for 8 seconds, the overload alarm will be detected and shown on the LED display (ALE06). Then, Servo Fault signal will be ON (DO signal ALRM will be activated).

Reserved

Communication Addr.: 0139H

 

 

 

 

Reserved

Communication Addr.: 013AH

 

 

 

 

Reserved

Communication Addr.: 013BH

 

 

 

 

Reserved

Communication Addr.: 013CH

 

 

 

 

Reserved

Communication Addr.: 013DH

 

 