4. Troubleshooting (DeviceNet)

♦ Causes of Error

Possible Cause

 

Examination Method

 

Countermeasure

{ Voltage drop of

Measure voltage of

 

 

 

Check voltage of the power

communications

communications power supply at

supply.

power supply

the master unit.

 

 

 

 

 

→ Normal: 11V or more between

 

 

V+ and V-

 

 

 

 

 

z If the voltage is 11 to 14 V, the

 

 

master unit is a possible cause.

 

 

Fix the problem on it.

 

 

 

{ Disconnected

(1)

Check that terminating

 

Fix the problem.

terminating

 

resistors are connected to

 

 

resistors

 

both ends of the network.

 

How to find the trouble

{ Cable

(2)

Measure resistance between

point:

disconnection

 

signal wires with

 

 

 

Remove the terminating

{ Disconnected

 

communications power

 

resistor on one end of the

connector

 

supply OFF.

 

 

 

network. The trouble point

{ Disconnected

→ Normal: 50 to 70

 

 

is where resistance

signal wire

z Measuring point: Connection

 

changes from 120 .

 

of the master

 

 

 

 

 

z For detail, refer to the section

 

 

4.1.3.1 Connection Problem.

 

 

{ Loose connector

Check for the connection of

 

Connect the connectors

{ Loose signal wire

connectors and signal wires.

 

and signal wires again.

 

→ The connectors and signal

 

 

 

wires should be firmly

 

 

 

 

connected.

 

 

 

 

 

z Checkpoint: Between the

 

 

 

master and its slaves

 

 

 

 

z For details, refer to the section

 

 

4.1.3.2 Loose Connector and

 

 

 

Signal Wire.

 

 

 

 

{ All slaves power

Measure the power voltage of the

Supply power to the slaves.

OFF

slaves. (It should be within the

 

 

 

range of sufficient voltage for

 

 

 

slave operation.)

 

 

 

 

{ Master unit

(1)

Start applicomIO

Console

Change the configuration.

configuration

 

application and check that the

 

 

 

configuration

has

no

 

 

 

difference with

the

network

 

 

 

condition.

 

 

 

 

 

(2) Check that the configuration

 

 

 

data were written in flash.

 

 

 

z For details, refer to the section

 

 

4.1.3.6 EPSON RC+ Master

 

 

 

Configuration.

 

 

 

 

90

Fieldbus I/O Rev.6

Page 102