4. Troubleshooting (PROFIBUS DP)
♦ Causes of Error |
|
|
| |
| Possible Cause |
| Examination Method | Countermeasure |
| { Disconnected | (1) | Check that terminating | Fix the problem. |
| terminating resistors |
| resistors are connected to |
|
| { Cable disconnection |
| both ends of the network. | How to find the trouble |
| { Disconnected | (2) | Measure resistance between | point: |
| connector |
| signal wires with device | Remove the terminating |
| { Disconnected signal |
| power supply OFF. | resistor on one end of the |
| wire | → Normal: 100 to 120 Ω | network. The trouble point | |
|
| z Measuring point: Connection | is where resistance | |
|
| of the trouble unit | changes from 220 Ω. | |
|
| z For detail, refer to the section |
| |
|
| 4.2.3.1 Connection Problem. | Connect the connectors | |
| { Loose connector | Check for the connection of | ||
| { Loose signal wire | connectors and signal wires. | and signal wires again. | |
|
| → The connectors and signal |
| |
|
| wires should be firmly |
| |
|
| connected. |
| |
|
| z Checkpoint: all stations and all |
| |
|
| branch taps |
| |
|
| z For details, refer to the section |
| |
|
| 4.2.3.2 Loose Connector and |
| |
|
| Signal Wire. | Take countermeasures | |
| { Noise | Check the noise intrusion via the | ||
| (external cause) | following paths (1) to (3). | against noise. | |
|
| (1) | Noise via shield |
|
|
| (2) | Induced noise via |
|
|
|
| communication cable |
|
|
| (3) | Device power supply |
|
|
| → For details, refer to the section |
| |
|
| 4.2.3.3 Noise Intrusion. | Replace the unit with a | |
| { Broken unit | Replace the trouble unit with a | ||
|
| new one. | new one. | |
|
| → Verify whether the problem is |
| |
|
| fixed. |
| |
| z No cause is | Identify the trouble point by |
| |
| identified. | dividing the network. |
| |
|
| → For details, refer to the section |
| |
|
| 4.2.3.4 Broken Unit |
| |
|
| Examination. |
|
Fieldbus I/O Rev.6 | 125 |