4. Troubleshooting (PROFIBUS DP)

4.2.2.4 Master: Configuration Error

Master Unit LED

Error

Description

BF

ST

 

 

Red Light

No

Physical error

- Nonstandard wiring

ON

Matter

 

- Signal wire connection failure

 

 

 

- Signal wire short circuit

Process Flowchart

Check

8

 

 

 

Check the following:

Problem exists. (Fix it.)

† No Problem

 

- Unconnected terminating resistor

 

- Unconnected or loose connector/signal wire

 

 

 

- Cable disconnection

See 4.2.3.1 and 4.2.3.2.

 

 

 

 

 

No problem

 

† No Change

 

Replace moving cable.

The problem is fixed.

 

 

 

(Replace deteriorated cable).

 

 

 

No change

 

† The trouble unit is not found.

 

 

Rarely

Does an error occur immediately?

 

 

 

 

 

 

Immediately

 

 

 

Divide the network and

The unit is found.

 

 

 

 

 

find the trouble unit.

 

 

 

The unit is not found.

Replace the unit.

 

 

 

Yes

 

 

 

Normal Communication?

 

 

 

No

 

 

Consult the PROFIBUS manufacturer.

Finish

128

Fieldbus I/O Rev.6

Page 140
Image 140
Epson EM07ZS1647F manual 128