2. Installation

PROFIBUS DP requires approximately 1ms at 12 Mbps for the transmission of 512 bits input data and 512 bits output data distributed over 32 stations. The following figure shows typical PROFIBUS DP transmission times depending on the number of stations and baud rate.

Bus Cycle Time [ms]

18

 

 

 

 

14

500 kbps

 

 

10

 

 

 

 

 

 

6

 

1.5 Mbps

 

 

2

 

12 Mbps

 

Number of Slaves

 

 

 

2

10

20

30

 

The maximum cable length is restricted by the baud rate.

Baud Rate

Maximum Cable Length

12 Mbps

100 m

6 Mbps

100 m

3 Mbps

100 m

1500 kbps

200 m

500 kbps

400 m

187.5 kbps

1000 m

93.75 kbps

1200 m

19.2 kbps

1200 m

9.6 kbps

1200 m

Multi-Master Configuration

PROFIBUS DP allows you to install multiple masters on a single physical network.

All slave devices on the network can be accessed by different masters. Only one master on the network can be used for device configuration.

The following figure illustrates the communication procedure for a multi-master configuration.

Token-passing Procedure

Master 1

Master 2

Master 3

Master-slave communication

Slave

Slave

Slave

Slave

Slave

Slave

Slave

When the master receives the logic token, it inquires data from its slaves. After all communications are completed, the master passes the token to another master. In this way, the master can only communicate with its slaves while it is holding the token. The slaves respond to only the inquiry from the master. No slave can output any messages.