4. Troubleshooting (DeviceNet)

♦ Causes of Error

Possible Cause

Examination Method

Countermeasure

{ Slave power OFF

Measure the power voltage of the

Supply power to the

 

slaves. (It should be within the range

slave.

 

of sufficient voltage for the slave

 

 

operation.)

 

 

NOTE: For slaves operating with

 

 

communications power

 

 

supply, measure voltage at

 

 

the DeviceNet connector.

 

{ Broken unit

Slave unit replacement

Replace the broken

 

 

slave unit with a new

 

 

one.

4.1.2.1.2 Slave: Communication Error Detection / Busoff Detection / Not-added

 

MS

NS

Master LED Condition

Green Light ON

Red Light Blinking

(1) Absent Slave LED Condition

Green Light ON

Red Light Blinking

(Communication error detection)

 

 

(2) Absent Slave LED Condition

Green Light ON

Red Light ON

(Busoff detection)

 

 

(3) Absent Slave LED Condition

Green Light ON

Light OFF

(Slave not added to the network)

 

 

Fieldbus I/O Rev.6

83

Page 95
Image 95