4. Troubleshooting (DeviceNet)
♦Process Flowchart
Check | 7 |
|
| Check for master unit | The problem is fixed. |
No Problem |
| configuration (scan list configuration). |
|
|
|
| |
|
| No problem |
|
|
| Check the following: |
|
|
| - Unconnected terminating resistor | Problem exists. (Fix it.) |
No Problem |
| - Unconnected or loose connector/signal wire | See 4.1.3.1 and 4.1.3.2. |
|
| - Cable disconnection | |
|
| No problem |
|
|
| Measure voltage of | Problem exists. (Fix it.) |
No Problem |
| communications power supply. |
|
|
| No problem |
|
No Change |
| Replace moving cable | The problem is fixed. |
|
| (Replace deteriorated cable). |
|
|
| No change |
|
No Change |
| Check for noise influence. | The problem is fixed. |
|
|
| |
|
|
| See 4.1.3.3. |
|
| No change |
|
|
| Replace the master unit. | The problem is fixed. |
No Change |
|
| |
|
|
| |
|
| No change |
|
The trouble unit is not found. |
| ||
| Rarely | Does an error occur immediately? |
|
|
|
| |
|
| Immediately |
|
|
| Divide the network and | The unit is found. |
|
| find the trouble unit. |
|
|
| The unit is not found. | Replace the unit. |
|
|
| Yes |
|
|
| Normal Communication? |
|
|
| No |
|
| Analyze the network with NetMeter. |
|
|
| Consult the DeviceNet manufacturer. | Finish |