4. Troubleshooting (PROFIBUS DP)
4.2.2.2 Master: Data Link Layer Error
Master Unit LED | Error | Description | ||
BF | ST | |||
|
| |||
Light | Red | Data link layer | - Nonstandard wiring | |
OFF | Light ON | error | - Noise intrusion | |
|
|
|
|
♦Process Flowchart
Check | 6 |
|
|
| Check the following: | Problem exists. (Fix it.) |
|
No Problem |
| - Unconnected terminating resistor |
| |
| - Unconnected or loose connector/signal wire |
|
| |
|
| - Cable disconnection | See 4.2.3.1 and 4.2.3.2. | |
|
| No problem |
|
|
No Change |
| Replace moving cable. | The problem is fixed. |
|
|
|
| ||
| (Replace deteriorated cable). |
|
| |
|
| No change |
|
|
|
| Check for noise influence. | The problem is fixed. |
|
No Change |
| See 4.2.3.3. | ||
|
|
| ||
|
| No change |
|
|
The trouble unit is not found. |
|
| ||
| Rarely | Does an error occur immediately? |
|
|
|
|
|
| |
|
| Immediately |
|
|
|
| Divide the network and | The unit is found. |
|
|
| find the trouble unit. |
|
|
|
| The unit is not found. | Replace the unit. |
|
|
|
|
| |
|
|
| Normal Communication? | Yes |
|
|
|
| |
|
|
| No |
|
|
| Consult the PROFIBUS manufacturer. |
| Finish |