4. Troubleshooting (PROFIBUS DP)

4.2.3 Procedures for Examining Possible Causes

4.2.3.1Connection Problem (Disconnected Terminating Resistors, Cable Disconnection, Disconnected Connector, Disconnected Signal Wire)

(1)Ensure that two terminating resistors are connected to both ends of the network.

(2)Turn OFF all device power supplies.

(3)Measure resistance between A1 and B1 wires of the absent slave using the tester.

Tester

Measure resistance between signal wires with tester.

Resistance

Determination

0

Shot circuit

Under 100

Three or more terminating resistors on one network

100 to 120

Normal

Over 120

Error (cable disconnection, disconnected signal wire, one or

 

zero terminating resistor)

(4) How to find the trouble point:

- Remove the terminating resistor on one end of the network.

(The resistance at the point where the terminating resistor is connected is 220 .)

-Measure resistance at branch taps of all units.

-The trouble point is where resistance changes from 220 .

-After finding the trouble point, verify the connector and cable conditions.