2. Installation
Thick Cable | Thin Cable |
11.2 to 12.1 mm outside diameter
Shield Wire
Braid Shield |
|
| 6.9 mm outside diameter | |||||||||||||
|
| |||||||||||||||
|
|
|
|
| Signal Wire |
|
|
|
|
| Braid Shield | |||||
|
|
|
|
|
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
| |||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| Signal Wire | |
|
|
|
|
| (Blue/White) |
|
|
|
|
|
|
|
|
|
| (Blue/White) |
|
|
|
|
| Power Wire |
|
|
|
|
|
|
|
|
|
| Power Wire |
|
|
|
|
| (Red/Black) | Shield Wire |
|
|
|
|
|
|
| (Red/Black) | ||
|
|
|
|
|
|
|
Communication Cable Signal
Wire Type | Color | Details of Signal | Wire Identity | |||
Signal wire | Blue | Signal |
| Low | CAN L | |
White | Signal | High | CAN H | |||
| ||||||
Power wire | Red | Communications Power |
| Positive | V+ | |
Black | Communications Power | Negative | V | |||
| ||||||
Shield wire | - | Shield |
|
| S |
Terminating Resistor
To reduce reflections of communication signal, terminating resistors should be attached on both ends of the trunk line. For DeviceNet, nodes have no terminating resistor on the ends.
Attach 121 Ω
L)of the trunk line cable. Some
Node Connection
Nodes can be connected to a DeviceNet network by the following topologies: tree,
Terminating |
| Branch Tap Terminating |
Resistor | Trunk Line | Resistor |
|
| Daisy Chain |
Tree
Communications Power Supply
DeviceNet supplies 24V DC communications power to each node via
Shield Ground of Signal Wire
Ground the DeviceNet network at one point with 100 Ω or less.
As a noise countermeasure, you can leave the network ungrounded. For details, refer to the 4. Troubleshooting.
Fieldbus I/O Rev.6 | 13 |