2. Installation

Thick Cable

Thin Cable

11.2 to 12.1 mm outside diameter

Shield Wire

Braid Shield

 

 

6.9 mm outside diameter

 

 

 

 

 

 

 

Signal Wire

 

 

 

 

 

Braid Shield

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Signal Wire

 

 

 

 

 

(Blue/White)

 

 

 

 

 

 

 

 

 

 

(Blue/White)

 

 

 

 

 

Power Wire

 

 

 

 

 

 

 

 

 

 

Power Wire

 

 

 

 

 

(Red/Black)

Shield Wire

 

 

 

 

 

 

 

(Red/Black)

 

 

 

 

 

 

 

Communication Cable Signal

Wire Type

Color

Details of Signal

Wire Identity

Signal wire

Blue

Signal

 

Low

CAN L

White

Signal

High

CAN H

 

Power wire

Red

Communications Power

 

Positive

V+

Black

Communications Power

Negative

V

 

Shield wire

-

Shield

 

 

S

Terminating Resistor

To reduce reflections of communication signal, terminating resistors should be attached on both ends of the trunk line. For DeviceNet, nodes have no terminating resistor on the ends.

Attach 121 +/-1%, 1/4W terminating resistors between the signal wires (CAN-H and CAN-

L)of the trunk line cable. Some T-branch taps and connectors can accept terminal resistors. Molded terminating resistors with connectors are also available to attach to environment- resistant T-branch taps and connectors.

Node Connection

Nodes can be connected to a DeviceNet network by the following topologies: tree, multi-drop, T-branch, daisy chain. For tree topology, there is no limitation of daisy chain layer but drop line length is limited. For details of drop line length, refer to the following section “Drop Line Length”.

Terminating

 

Branch Tap Terminating

Resistor

Trunk Line

Resistor

 

 

Daisy Chain

Tree Multi-drop T-branch

Communications Power Supply

DeviceNet supplies 24V DC communications power to each node via 5-wire cables. You can install the communications power supply at any location on the DeviceNet network. We recommend providing a dedicated communications power supply on the network separately even though it is possible to share power among the communications power supply, node internal circuit power supply, and I/O power supply.

Shield Ground of Signal Wire

Ground the DeviceNet network at one point with 100 or less.

As a noise countermeasure, you can leave the network ungrounded. For details, refer to the 4. Troubleshooting.

Fieldbus I/O Rev.6