4. Troubleshooting (DeviceNet)
♦ Causes of Error |
|
|
|
|
|
| Countermeasure |
| |
| Possible Cause |
| Examination Method |
|
| ||||
| { Voltage drop of | Measure voltage of |
|
|
| Check voltage of the power |
| ||
| communications | communications power supply at | supply. |
| |||||
| power supply | the master unit. |
|
|
|
|
| ||
|
| → Normal: 11V or more between |
|
| |||||
|
| V+ and V- |
|
|
|
|
| ||
|
| z If the voltage is 11 to 14 V, the |
|
| |||||
|
| master unit is a possible cause. |
|
| |||||
|
| Fix the problem on it. |
|
|
|
| |||
| { Disconnected | (1) | Check that terminating |
| Fix the problem. |
| |||
| terminating resistors |
| resistors are connected to |
|
|
| |||
| { Cable disconnection |
| both ends of the network. |
| How to find the trouble |
| |||
| { Disconnected | (2) | Measure resistance between |
| |||||
| point: |
| |||||||
| connector |
| signal wires with |
|
|
|
| ||
|
|
|
|
| Remove the terminating |
| |||
| { Disconnected signal |
| communications power |
|
| ||||
| wire |
| supply OFF. |
|
|
| resistor on one end of the |
| |
|
| → Normal: 50 to 70 Ω |
|
| network. The trouble point |
| |||
|
| z Measuring point: Connection | is where resistance |
| |||||
|
| of the master |
|
|
| changes from 120 Ω. |
| ||
|
| z For detail, refer to the section |
|
| |||||
|
| 4.1.3.1 Connection Problem. |
|
| |||||
| { Loose connector | Check for the connection of |
| Connect the connectors |
| ||||
| { Loose signal wire | connectors and signal wires. |
| and signal wires again. |
| ||||
|
| → The connectors and signal |
|
| |||||
|
| wires | should | be | firmly |
|
| ||
|
| connected. |
|
|
|
|
| ||
|
| z Checkpoint: Between the |
|
|
| ||||
|
| master and its slaves |
|
|
|
| |||
|
| z For details, refer to the section |
|
| |||||
|
| 4.1.3.2 | Loose Connector | and |
|
| |||
|
| Signal Wire. |
|
|
|
|
| ||
| { All slaves power | Measure the power voltage of the | Supply power to the slaves. |
| |||||
| OFF | slaves. |
|
|
|
|
|
| |
|
| (It should be within the range of |
|
| |||||
|
| sufficient voltage for slave |
|
|
| ||||
|
| operation.) |
|
|
|
|
| ||
| { Master unit | (1) | Start | applicomIO | Console | Change the configuration. |
| ||
| configuration |
| application and | check | that |
|
| ||
|
|
| the | configuration | has | no |
|
| |
|
|
| difference with | the | network |
|
| ||
|
|
| condition. |
|
|
|
|
| |
|
| (2) | Check that the configuration |
|
| ||||
|
|
| data were written in flash. |
|
| ||||
|
| z For details, refer to the section |
|
| |||||
|
| 4.1.3.6 EPSON RC+ Master |
|
| |||||
|
| Configuration. |
|
|
|
|
|
Fieldbus I/O Rev.6 | 97 |