4. Troubleshooting (PROFIBUS DP)
| 4.2.2.1.3 Slave: Uninitialized Network |
|
| |
|
|
| BF | ST |
|
| Master LED Condition | Light OFF | Red Light Blinking |
|
| Absent Slave LED Condition | Light OFF | Light OFF |
|
| (Uninitialized Network) | ||
|
|
|
| |
♦ Process Flowchart |
|
| ||
Check | 4 |
|
| |
|
|
|
No Problem | Measure voltage of all | Problem exists. (Fix it.) | ||||
|
|
| ||||
slave power supplies. |
|
|
| |||
|
|
|
| |||
|
| No problem |
|
|
| |
|
|
|
|
| ||
|
|
|
|
| ||
| Check the following: | Problem exists. (Fix it.) | ||||
No Problem | - Unconnected terminating resistor | |||||
- Unconnected or loose connector/signal wire |
|
|
| |||
|
|
| ||||
| - Cable disconnection |
| See 4.2.3.1 and 4.2.3.2. | |||
|
| No problem | The problem is fixed. | |||
|
| |||||
|
| |||||
| Replace moving cable. | |||||
No Change |
|
|
| |||
(Replace deteriorated cable). |
|
|
|
| ||
|
|
|
|
No change
Replace the unit.
Yes
No | Normal Communication? |
No
Consult the PROFIBUS manufacturer. | Finish |
Fieldbus I/O Rev.6 | 121 |