4. Troubleshooting (DeviceNet)

Status Code

General Protocol

45

47

53

55

65

70

79

63

66

93

99

255

Descriptions

Non-resident dialogue software. Additional information:

Initialize the applicomIO® interface before use by running the PcInitIO

Targeted applicomIO® card invalid or incorrectly initialized by the function IO_Init Synchronization problem on the line.

Additional information:

The DeviceNet master is "off line" (power supply not detected or the CAN component of the applicomIO® is "Bus Off")

Check the network wiring and Baud Rate. Response time-out exceeded.

Additional information:

The device accepted the connection but did not answer the request.

Check the device status. Connection denied. Additional information:

Connection to the DeviceNet master is in progress or refused by the device.

Connection finished. Additional information:

Duplication of MAC ID detected on the DeviceNet network.

Modify the MAC ID of the DeviceNet master. Profile incompatible.

Additional information:

The device does not match the configuration. Check the device identity and the connection sizes. Indicates that a communication error has been encountered on serial Port.

Not enough applicomIO® interface memory. Driver cannot be accessed.

Indicates that applicomIO® solution is already running.

Indicates that the local input buffer was not updated beforehand by the function IO_RefreshInput.

Fieldbus I/O Rev.6

109

Page 121
Image 121