Epson EM07ZS1647F manual Io Led, Status Code Descriptions General Protocol

Models: EM07ZS1647F

1 168
Download 168 pages 47.58 Kb
Page 120
Image 120

4. Troubleshooting (DeviceNet)

(2) Select the DeviceNet (Scanner) tab. The window changes as shown below.

MAC ID

:

MAC ID specified for the scanner board

Module/NetWork LED

:

Network Status (NS) LED status

IO LED

:

Module Status (MS) LED status

applicomR Status

:

Scanner board status

The scanner board status is shown in the “Code No. => Comment” form. The code numbers are shown in the following table.

Status Code

Descriptions

General Protocol

 

0

No fault detected. The function was performed

 

correctly.

4

Inaccessible data.

 

Additional information:

 

The remote device is in error.

 

Check its status.

32

Indicates that the parameters passed to the functions

 

are not correct (eg: Number of requested variables

 

too large)

33

Response time-out fault.

 

Additional information:

 

The device does not answer. Check its status and the

 

wiring.

 

The DeviceNet master has no device to be scanned in

 

its configuration.

34

Physical defect on the line.

 

Additional information:

 

No +24V power supply was detected.

 

The CAN component of the applicomIO® interface

 

is "Bus Off".

 

Check the network wiring and Baud Rate.

36

Device not configured.

 

Define the device configuration with the

 

applicomIO® Console and re-initiate the

 

initialization of the applicomIO® product by running

 

the PcInitIO

108

Fieldbus I/O Rev.6

Page 120
Image 120
Epson EM07ZS1647F manual Io Led, Status Code Descriptions General Protocol