4. Troubleshooting (DeviceNet)
(2) Select the DeviceNet (Scanner) tab. The window changes as shown below.
MAC ID | : | MAC ID specified for the scanner board | |
Module/NetWork LED | : | Network Status (NS) LED status | |
IO LED | : | Module Status (MS) LED status | |
applicomR Status | : | Scanner board status |
The scanner board status is shown in the “Code No. => Comment” form. The code numbers are shown in the following table.
Status Code | Descriptions | |
General Protocol | ||
|
0 | No fault detected. The function was performed |
| correctly. |
4 | Inaccessible data. |
| Additional information: |
| The remote device is in error. |
| Check its status. |
32 | Indicates that the parameters passed to the functions |
| are not correct (eg: Number of requested variables |
| too large) |
33 | Response |
| Additional information: |
| The device does not answer. Check its status and the |
| wiring. |
| The DeviceNet master has no device to be scanned in |
| its configuration. |
34 | Physical defect on the line. |
| Additional information: |
| No +24V power supply was detected. |
| The CAN component of the applicomIO® interface |
| is "Bus Off". |
| Check the network wiring and Baud Rate. |
36 | Device not configured. |
| Define the device configuration with the |
| applicomIO® Console and |
| initialization of the applicomIO® product by running |
| the PcInitIO |
108 | Fieldbus I/O Rev.6 |