4. Troubleshooting (PROFIBUS DP)

4.2.2 Problems and Countermeasures

Master Unit LED

Error

Description [Reference]

BF

ST

 

 

Light

Green

Normal

- Normal condition

OFF

Light

communication

 

 

Blinking

 

 

Light

Green

Ready for

- Normal condition

OFF

Light ON

communication

 

Light

Red

Communication

[Refer to the section 4.2.2.1 Master

Communication Error.]

OFF

Light

error

- Slave disconnected from the network

 

Blinking

 

 

 

(Remote I/O communication error)

 

 

 

 

 

 

- Slave not added to the network (Scan list

 

 

 

collation error)

 

 

 

- Nonstandard wiring

 

 

 

- No or too many terminating resistors

 

 

 

- Noise intrusion

Light

Red

Data link layer

[Refer to the section 4.2.2.2 Master: Data

OFF

Light ON

error

Link Layer Error.]

 

 

 

- Nonstandard wiring

 

 

 

- Noise intrusion

Light

Light

Uninitialized

[Refer to the section 4.2.2.3 Master:

OFF

OFF

network

Uninitialized Network.]

 

 

 

- Master unit power error

 

 

 

- Master unit configuration error

Red

No

Physical error

[Refer to the section 4.2.2.4 Master:

Light ON

Matter

 

Configuration Error.]

 

 

 

- Nonstandard wiring

 

 

 

- Signal wire connection failure

 

 

 

- Signal wire short circuit

114

Fieldbus I/O Rev.6

Page 126
Image 126
Epson EM07ZS1647F manual Link Layer Error