4. Troubleshooting (PROFIBUS DP)
4.2.1.2 Check Network Status
First of all, you should check the current condition of the network. There are different specifications of status display LED on a device in the PROFIBUS DP standard. This section explains how to check the network status assuming that EPSON RC+ is configured as a master or slave.
(1) Master Status: BF/ST LEDs |
|
|
|
|
| |
| LED | Color |
| Light Condition |
| |
| BF (Physical error) | Green | Red | ON | Blinking | OFF |
| ST (Communication Status) | Green | Red | ON | Blinking | OFF |
(2) Station Number of Absent Slaves
Absent slaves are disconnected from or not added to the network.
1.See the status flag regarding to the removal and addition if the master has status information.
2.See the BF/ST LEDs of all slaves if the master has no status information.
(3)Absent Slave Status: BF/ST LEDs
LED | Color |
| Light Condition |
| |
BF (Physical error) | Green | Red | ON | Blinking | OFF |
ST (Communication Status) | Green | Red | ON | Blinking | OFF |
(4) Physical Node Location of Absent Slave
Master PLC
Terminating Resistor ON
Slave Slave Slave
Terminating Resistor ON
Terminating
Resistor ON
Slave Slave Slave
Start the examination from this block when an error occurred here.
(5)Error Occurrence Condition
Immediate occurrence (high reproducibility)
Rare occurrence (low reproducibility)
Fieldbus I/O Rev.6 | 113 |