Table 12. DFSMS Messages Based on Library Failure or Exception Conditions (continued)

Resulting Console Message

Action

 

 

CBR3764E Library library-nameall storage cells full.

Cartridges must be ejected before any can be added to

All storage cells in library library-nameare occupied by,

the library. There is also an intervention-required

condition set for this condition. It is automatically cleared

or reserved for, cartridges that are already in the library.

when the library is no longer full.

No more cartridges can be added to the library.

 

Cartridges in the input station of the library cannot be

 

added to the library.

 

This message is retained on the console until the library

 

has available storage cells.

 

 

 

CBR3765E No cleaner volumes available in library

1. Choose Operator intervention from the Commands

library-name.

pull-down on the library manager console.

 

The library manager in library library-namemust perform

2. Find the intervention-required condition that identi®es

which type of cleaner cartridge the library requires.

a clean operation on one of the drives in the library, but

 

no compatible cleaner volumes are available in the

3. Place one or more compatible cleaner volumes, with

library.

bar-code labels that match the cleaner masks into the

This message is retained on the console until the library

convenience input station.

 

has at least one appropriate cleaner volume.

 

 

 

CBR3766E Dual write disabled in library library-name.

Contact your service representative.

The library manager in library library-nameis not

 

updating the secondary database for the library manager

 

inventory. This can be the result of a hardware failure.

 

Operations continue with the primary database.

 

 

 

CBR3769I Misplaced volume volser found in library

Resubmit the library request or job that failed because

library-name.

the volume was misplaced.

Library library-namefound volume volser, which had

 

previously been reported as misplaced. The library

 

manager updated the inventory to re¯ect the new location

 

of the volume.

 

 

 

CBR3770I Volume volser misplaced in library

1. Go to the library and ®nd the volume record in the

library-name.

database. (Choose Search database for volumes

 

During the execution of a library operation with volume

from the Database pull-down.)

2. Place the library in pause mode.

volser in library library-name, the volume cannot be found

at the location recorded in the library manager inventory.

3. Enter the library and ®nd the home cell the volume

 

should have been in and search for it in the

 

surrounding cells. If the database shows the volume

 

in a device, check that device. If you ®nd the volume,

 

leave the library and place the volume in the

 

convenience input station.

 

4. Place the library in auto mode.

 

5. Resubmit the library request or job after the input

 

station is inventoried.

 

 

CBR3771I Duplicate volume volser ejected from

1. Remove the ejected volume from the output station.

library library-name.

2. Determine why the volume has a duplicate label.

 

A volume was found in a library cell whose volser volser

3. Clear the item from the Intervention Required pop-up

is a duplicate of one already in library library-name. The

window. See Table 19 on page 288 for details.

location recorded in the library manager inventory for this

 

volser already contains a volume with the same volser;

 

this volume was ejected from the library to a convenience

 

output station.

 

 

 