Table21. Intervention Required Conditions relating to cleaner cartridges (continued)

Intervention Required Condition Resolution Actions
Message
The library is out of HPCT cleaner cartridges.
Probable Cause
Aclean operation for a 3590 type tape device needs to
be performed, but there are no available compatible
cleaner cartridges in the library.Either no cleaner
cartridges have been added to the library,or they have all
been used and have been ejected.
1. Place 3590 type cleaning cartridges in the
convenience I/O station.
2. This condition cannot be cleared by selecting it from
the list of actions. Instead, this condition is cleared
automatically by the library system when a cleaning
cartridges, of the appropriate type, are inserted by the
operator.
Message
A mislabeled cleaner cartridge has been ejected to
the convenience I/O station.
Probable Cause
An attempt was made to a clean a tape device but the
cartridge was determined to be a data cartridge, not a
cleaner cartridge. Either the cartridge was mistakenly
labeled with an external volser that falls within the range
of volsers designated for cleaner volumes in the library or
the ranges set in the library conflict with ranges already in
use for data cartridges.
1. Remove the cartridge from the convenience output
station.
2. Check if the volser on the cartridge is included in the
range(s) of volsers defined for cleaner cartridges
using the Cleaner Masks item from the Commands
pull-down on the library manager console.
3. Correct either the cleaner masks or relabel the
cartridge.
Message
A mislabeled cleaner cartridge has been ejected to
the high-capacity facility cell: yyyy.
Probable Cause
An attempt was made to a clean a tape device but the
cartridge was determined to be a data cartridge, not a
cleaner cartridge. The convenience I/O station was either
not installed, is full or is unavailable. Either the cartridge
was mistakenly labeled with an external volser that falls
within the range of volsers designated for cleaner
volumes in the library or the ranges set in the library
conflict with ranges already in use for data cartridges.
The cartridge is in H.F.C.cell yyyy.
1. Place the library system in pause mode.
2. Open the appropriate enclosure door.
3. Remove the cartridge from the high-capacity facility.
4. Close the enclosure door.
5. Place the library system in auto mode.
6. Check if the volser on the cartridge is included in the
range(s) of volsers defined for cleaner cartridges
using the Cleaner Masks item from the Commands
pull-down on the library manager console.
7. Correct either the cleaner masks or relabel the
cartridge.
294 Magstar 3494 TapeLibrary Operator Guide