Juniper Networks manual Grounding Cable Lug For an EX8208 Switch

Models: EX8208

1 338
Download 338 pages 53.12 Kb
Page 114
Image 114

Complete Hardware Guide for EX8208 Ethernet Switches

NOTE: Grounding is provided to an AC-powered switch when you plug its power supplies into grounded AC power receptacles.

Figure 32 on page 88 shows the cable lug that attaches to the grounding cable in an

EX8208 switch.

Figure 32: Grounding Cable Lug For an EX8208 Switch

The grounding cable that you provide for an EX8208 switch must be 6 AWG (13.3 mm2), minimum 60°C wire, or as permitted by the local code.

The grounding cable that you provide for an EX8216 switch must be 2 AWG (33.6 mm2), minimum 60°C wire, or as permitted by the local code.

NOTE: Two grounding lugs for an EX8216 switch are shipped with the chassis.

WARNING: The switch is pluggable type A equipment installed in a restricted-access location. It has a separate protective earthing terminal provided on the chassis in addition to the grounding pin of the power supply cord. This separate protective earthing terminal must be permanently connected to earth ground for installations that require a separate grounding conductor to the chassis.

Related Topics AC Power Supply in an EX8200 Switch on page 40

DC Power Supply in an EX8200 Switch on page 48

Connecting AC Power to an EX8200 Switch on page 173

Connecting DC Power to an EX8200 Switch on page 175