Setup Menu

A.6.3 Setup Sensor

For details on this feature, see 9.5 - Setup System - Setup Sensor.

Setup Sensor

SETUP SENSOR

Setup for analog

input points

Select sensor to edit

SENSOR

VALUE

1=SENSOR_1

80.0

DEG

2=SENSOR_2 ------

DEG

3=SENSOR_3

80.0

DEG

4=SENSOR_4

79.5

RH

5=RETURN TO SETUP MENU 6=RETURN TO MAIN MENU

SELECT A NUMBER:1

>IS THE SENSOR CONNECTED-YES(Y) OR NO(N)? >[N]

>[

>COMMAND SUCCESSFUL

>CHANGE SENSOR LABEL(8 CHARACTERS MAX). >[SENSOR_1]

>[

>COMMAND SUCCESSFUL

>CHANGE UNITS LABEL(3 CHARACTERS MAX). >[DEG]

>[

>COMMAND SUCCESSFUL

>CHANGE 4 mA VALUE(-999.9 to 999.9). >[-020.0] >[

>COMMAND SUCCESSFUL

>CHANGE 20 mA VALUE(-999.9 to 999.9). >[+020.0]

109

Page 117
Image 117
Liebert Universal Monitor user manual Setup Sensor