System and Control Options

9.6.2Set Up Mapping for an Analog Sensor Input

Use the arrows ↑ ↓to choose Map Sensor To Outpt from the Map Input/Sensor Menu, and press Enter .

From the Select Sensor Menu, choose the input you want—for example, Sensor_1 High Stpt—and press Enter .

Map Sensor to Main Board Output

From the Select Outputs menu, select Map to Main Board if you want to map the selected sensor to an output on the Universal Monitor main board. These outputs are identified as Outputs 1-8.

On the Output Map screen, you may map the selected sensor to any of the eight outputs (1-8)—or to more than one output, if desired. The example at right shows Sensor_1 High Stpt mapped to Output04.

To make changes to the mapping:

If needed, press Enter to advance to the position directly below the output.

Use the arrows ↑ ↓to choose Y (Yes - Mapped to this output) or N (No - Not mapped), then press Enter .

Press Enter to advance to the next position where you want to make a change.

Use the arrows ↑ ↓to choose Y (Yes - Mapped to this output) or N (No - Not mapped), then press Enter .

When finished, press Enter again.

Map Sensor to Expansion Board Output

From the Select Outputs menu, select Map to Exp Board if you want to map the selected sensor to an output on the optional Expansion Board. These outputs are identified as Outputs 9-16.

On the Output Map screen, you may map the selected sensor to any of the eight outputs (9-16)—or to more than one output, if desired. The example at right shows Sensor_1 High Stpt mapped to Output11.

To make changes to the mapping:

If needed, press Enter to advance to the position directly below the output.

Use the arrows ↑ ↓to choose Y (Yes - Mapped to this output) or N (No - Not mapped), then press Enter .

Press Enter to advance to the next position where you want to make a change.

Use the arrows ↑ ↓to choose Y (Yes - Mapped to this output) or N (No - Not mapped), then press Enter .

When finished, press Enter again.

Map Input/Sensor Menu

MAP INPUT TO OUTPUT

> MAP SENSOR TO OUTPT

↑ ↓=NEXT =SELECT

Select Sensor

SELECT SENSOR

> SENSOR_1 HIGH STPT

SENSOR_1 LOW STPT

↑ ↓=NEXT

=SELECT

SENSOR_2 HIGH STPT SENSOR_2 LOW STPT SENSOR_3 HIGH STPT SENSOR_3 LOW STPT SENSOR_4 HIGH STPT SENSOR_4 LOW STPT

Select Outputs

SELECT OUTPUTS

>MAP TO MAIN BOARD MAP TO EXP BOARD

=SELECT↑ ↓=NEXT

Output Map

1H OUTPUT

MAP

 

1 2 3

4

5

6

7

8

N N N

Y

N

N

N N

=Y/N =NEXT/END

Select Outputs

SELECT OUTPUTS MAP TO MAIN BOARD

> MAP TO EXP BOARD

↑ ↓=NEXT

=SELECT

Output Map

1H OUTPUT MAP

0910111213141516 N N Y N N N N N

=Y/N =NEXT/END

Default Mappings - Analog Inputs to Outputs

By default, analog inputs are not mapped to any digital output, as shown in Table 24.

Table 24 Default mapping of analog inputs to digital outputs

Analog input

By default, mapped to digital output:

 

 

Sensor_1

(none)

 

 

Sensor_2

(none)

 

 

Sensor_3

(none)

 

 

Sensor_4

(none)

 

 

57

Page 65