System and Control Options

9.2Setup System - Overview

The Setup System screen displays seven options that allow you to configure input and output devices and their relationships, the common alarm, the modem, pagers to be dialed when alarms occur, and a variety of system details, such as login password and system date and time:

Setup Input

Setup Common Alarm

Setup Sensor

Setup I/O Matrix

Setup Output

Setup Modem & Pagers

Setup System Info

Setup Exp Board

Setup System Menu

>SETUP INPUT

SETUP COMMON ALARM SETUP SENSOR

SETUP I/O MATRIX

↑ ↓=NEXT =SELECT

SETUP OUTPUT SETUP MODEM&PAGERS SETUP SYSTEM INFO SETUP EXP BOARD

9.3Setup System - Setup Input

The Universal Monitor has eight digital input points that may be configured individually. If the optional Expansion Board is used, an additional 16 digital inputs may also be configured. These inputs may have a wide variety of Liebert or other manufacturers’ equipment connected for monitoring.

To configure a digital input:

Log In and Choose Setup System

From the Main Menu, use the arrows ↑ ↓ to choose System and Control, then press Enter (see 9.1 - Login for help).

Enter your password at the Login screen.

From the System and Control Menu, use the arrows ↑ ↓ to choose Setup System, then press Enter .

Select a Digital Input to Configure

From the Setup System Menu, shown at right, use the arrows ↑ ↓to choose Setup Input and press Enter .

From the Select Input Menu, choose the input you want—for exam- ple, Input_01—and press Enter .

Table 21 shows the digital input features you may change, along with the default settings: you may change the name of the input, define it as normally open or closed, and specify it as alarmable or as an event.

• Alarmable inputs may be defined as either Unlatched or Latched.

Select Input Menu

SELECT INPUT

>INPUT_01 NO-AL-NL INPUT_02 NO-AL-NL

=SELECT↑ ↓=NEXT

INPUT_03 NO-AL-NL INPUT_04 NO-AL-NL INPUT_05 NO-AL-NL INPUT_06 NO-AL-NL INPUT_07 NO-AL-NL INPUT_08 NO-AL-NL INPUT_09 NO-AL-NL INPUT_10 NO-AL-NL INPUT_11 NO-AL-NL INPUT_12 NO-AL-NL INPUT_13 NO-AL-NL INPUT_14 NO-AL-NL INPUT_15 NO-AL-NL INPUT_16 NO-AL-NL INPUT_17 NO-AL-NL INPUT_18 NO-AL-NL INPUT_19 NO-AL-NL INPUT_20 NO-AL-NL INPUT_21 NO-AL-NL INPUT_22 NO-AL-NL INPUT_23 NO-AL-NL INPUT_24 NO-AL-NL

NOTE: INPUT_09 - INPUT_24 for optional Expansion Board

Event status allows you to monitor a digital input’s state—and use a change in state to initiate an action through an output, if desired—without triggering an alarm. Events are always Unlatched.

You may also specify a time delay before the Universal Monitor responds to an alarm or event.

Use the steps following Table 21 to change the default settings for any digital input.

Table 21 Default settings - digital inputs

Feature

Default

Other Options

LABEL

INPUT_01

Any name (up to eight characters)

NORM OPEN/CLOSE

NO (Normally open)

NC (Normally closed)

ALARM/EVENT

AL (Alarmable)

EV (Event)

LATCHED

NL (Unlatched) / N (No)*

L (Latched) / Y (Yes)*

DELAY

00:01 (1 second)

Any time (in minutes and seconds) from 00:00 to 99:59

* NOTE: Different abbreviations are used to designate a digital input as Latched or Unlatched as shown below.

 

Settings - Select Input Menu

When configuring an input

 

(see Section 9.3)

(see Section 9.3.4)

Unlatched

NL (Not Latched)

N (No, not latched)

Latched

L (Latched)

Y (Yes, latched)