Wiring and Connections - Optional Expansion Board

5.2.3Setting the Digital Output DIP Switches

Each digital output on the optional Expansion Board has an associated DIP switch that can deter- mine its operation in the event of loss of communication with the Universal Monitor or loss of power.

When the Universal Monitor calls for an Expansion Board output to be ON, it sends a command to the Expansion Board to turn the output to the ON state; this is signified by the output LED being ON. The behavior of the output when it is ON is determined by the position of the DIP switch.

The DIP switches for the outputs are on a switch bank on the right side of the Expansion Board, as shown below. Each switch corresponds to an output on the board in order from left to right—for exam- ple, DIP switch 1 corresponds to Output 9; DIP switch 2 corresponds to Output 10.

Optional

Expansion

Board

EIA485 + (to UM-)

0V EIA485 - (to UM+)

USE COPPER (CU) CONDUCTORS ONLY.

POWER INPUT

RELAY OUTPUTS

D6

-8103065

 

V2

V4

V6

V8

V10

V12

V14

V16

 

V1

V3

V5

 

V7

V9

V11

V13

V15

 

168AOMultiflex

 

 

 

 

 

 

 

 

S4

S3

S2

S1

 

 

 

 

 

 

 

 

Digital output

 

 

 

K1

K2

K3

K4

K5

K6

K7

K8

 

 

 

 

OUT1

OUT2

 

OUT3

OUT4

OUT5

OUT6

OUT7

OUT8

DIP switches

 

 

 

 

 

 

 

 

 

 

 

 

DEFAULT SETTINGS FOR USE WITH UNIVERSAL MONITOR

Tables 10 and 11 show how to set the DIP switch for each output based on how the output is wired (see 5.2.2 - Connecting Digital Outputs) and how you want it to perform during normal operation, when communication with the Universal Monitor is lost or when power fails.

NOTE

After a loss of communications with the Universal Monitor, there is a time delay—about five minutes—before the Expansion Board changes the state of an output.

Table 10 DIP switch setting - outputs wired as Normally Closed (N.C.)

If Output

 

State of Output When:

 

 

 

 

 

DIP Switch

Light is

Light is

Communication

Power

is:

ON

OFF

with UM is Lost

Fails

Up (ON)

Closed

Open

Closed

Closed

 

 

 

 

 

Down (OFF)

Open

Closed

Closed

Closed

 

 

 

 

 

N.C.

N.O.

Wire connected to N.C. terminal

Table 11 DIP switch setting - outputs wired as Normally Open (N.O.)

If Output

 

State of Output When:

 

 

 

 

 

DIP Switch

Light is

Light is

Communication

Power

is:

ON

OFF

with UM is Lost

Fails

Up (ON)

Open

Closed

Open

Open

 

 

 

 

 

Down (OFF)

Closed

Open

Open

Open

 

 

 

 

 

N.C.

N.O.

Wire connected to N.O. terminal

The Expansion Board comes from the factory with all digital output DIP switches in the OFF position (normally open). The DIP switch setting for each digital output can be changed to ON (normally closed).

To change the state of any output to the factory default of NO (Normally Open) or to NC (Normally Closed), move each switch to the appropriate position:

Move the switch down to the OFF position for NO (Normally Open)—the default setting.

Move the switch up to the ON position for NC (Normally Closed).