Specifications

10.0SPECIFICATIONS

10.1Universal Monitor Specifications

 

Small Enclosure

 

Large Enclosure

 

 

 

 

 

 

UMS02400

 

115VAC

230VAC

Power

 

UML11500

UML23000

 

 

Requirements

 

 

 

 

24VAC ±10%

 

115VAC ±10%

230VAC ±10%

 

of nominal;

 

of nominal;

of nominal;

 

50/60 Hz, 1.3A,

 

60Hz, 4A,

50Hz, 0.5A,

 

30VA

 

460VA

115VA

Dimensions

14-1/4 x 2-3/4 x 12

 

18 x 2-3/4 x 18

W x D x H, in. (mm)

(361.95 x 69.85 x 304.8)

 

(457.2 x 69.85 x 457.2)

Weight (Assembled)

7.68 lb. (3.48 kg)

 

20.56 lb. (9.33 kg)

Enclosure Type

NEMA 1

 

Liquid Crystal Display (LCD)

Four line, 20 character, backlit

 

Mounting Surface

Building Wall or Structural Member

Ambient Operating

32ºF to 104ºF (0ºC to 40ºC)

 

Environment

0% RH to 95% RH (non-condensing)

Processor Specifics

 

 

 

 

Model

Motorola XC68HC812A4

 

Clock speed

 

16MHz

 

Total RAM

 

256Kb

 

Total FLASH

 

4M

 

Total EEPROM

 

4K

 

A/D Resolution (Analog IN)

 

12 Bit

 

Modem Type

Embedded 14.4K bps

 

Clock Type

Real-Time Clock

 

Clock battery backup type

Lithium Cell (non-replaceable)

 

Clock battery life

7 years, constant, no power

 

Modem battery backup type

Nickel Cadmium (replaceable)

 

Modem battery life

10 minutes at full load

 

Communications

 

 

 

 

Local Communications

 

RS232

 

Remote Communications

 

 

 

 

Modem (9600-N-8-1)

Baud rate 9600 bps, Parity=None, Data bits=8, Stop bits=1

Supported pagers

9600 E-7-1 supports TAPI protocol version 1.8

SiteScan Web

IGM Protocol, EIA422

 

Expansion Board (optional)

 

EIA485

 

 

No Transformer Module

 

With Transformer Module

Agency Listings

 

 

 

 

(UMS02400)

 

115VAC

230VAC

 

 

(TM115)

(TM230)

 

 

 

 

 

 

 

 

UL

UL3121

 

UL1012

UL1585

CSA

C22.2 No. 1010

 

C22.2 No. 66 and

 

C22.2 No. 107.1

 

 

 

CE

Yes

 

Yes

FCC Compliance

CFR 47 Part 15

 

N/A

Inputs & Outputs (Quantity)

 

 

 

 

Digital Inputs (8)

Dry Contact Closure 24VDC, 10 mA

Analog Inputs (4)

4-20 mA signal input with selectable

power source of 12VDC or 24VDC

 

Digital Outputs (8)

24VAC, 3A

 

Common Alarm Outputs (2)

24VAC, 3A

 

NOTE

If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.

83

Page 91
Image 91
Liebert user manual Universal Monitor Specifications