Specifications
10.0SPECIFICATIONS
10.1Universal Monitor Specifications
| Small Enclosure |
| Large Enclosure | ||
|
|
|
|
| |
| UMS02400 |
| 115VAC | 230VAC | |
Power |
| UML11500 | UML23000 | ||
|
| ||||
Requirements |
|
|
|
| |
24VAC ±10% |
| 115VAC ±10% | 230VAC ±10% | ||
| of nominal; |
| of nominal; | of nominal; | |
| 50/60 Hz, 1.3A, |
| 60Hz, 4A, | 50Hz, 0.5A, | |
| 30VA |
| 460VA | 115VA | |
Dimensions |
| 18 x | |||
W x D x H, in. (mm) | (361.95 x 69.85 x 304.8) |
| (457.2 x 69.85 x 457.2) | ||
Weight (Assembled) | 7.68 lb. (3.48 kg) |
| 20.56 lb. (9.33 kg) | ||
Enclosure Type | NEMA 1 |
| |||
Liquid Crystal Display (LCD) | Four line, 20 character, backlit |
| |||
Mounting Surface | Building Wall or Structural Member | ||||
Ambient Operating | 32ºF to 104ºF (0ºC to 40ºC) |
| |||
Environment | 0% RH to 95% RH | ||||
Processor Specifics |
|
|
|
| |
Model | Motorola XC68HC812A4 |
| |||
Clock speed |
| 16MHz |
| ||
Total RAM |
| 256Kb |
| ||
Total FLASH |
| 4M |
| ||
Total EEPROM |
| 4K |
| ||
A/D Resolution (Analog IN) |
| 12 Bit |
| ||
Modem Type | Embedded 14.4K bps |
| |||
Clock Type |
| ||||
Clock battery backup type | Lithium Cell |
| |||
Clock battery life | 7 years, constant, no power |
| |||
Modem battery backup type | Nickel Cadmium (replaceable) |
| |||
Modem battery life | 10 minutes at full load |
| |||
Communications |
|
|
|
| |
Local Communications |
| RS232 |
| ||
Remote Communications |
|
|
|
| |
Modem | Baud rate 9600 bps, Parity=None, Data bits=8, Stop bits=1 | ||||
Supported pagers | 9600 | ||||
SiteScan Web | IGM Protocol, EIA422 |
| |||
Expansion Board (optional) |
| EIA485 |
| ||
| No Transformer Module |
| With Transformer Module | ||
Agency Listings |
|
|
|
| |
(UMS02400) |
| 115VAC | 230VAC | ||
|
| (TM115) | (TM230) | ||
|
|
| |||
|
|
|
|
| |
UL | UL3121 |
| UL1012 | UL1585 | |
CSA | C22.2 No. 1010 |
| C22.2 No. 66 and | ||
| C22.2 No. 107.1 | ||||
|
|
| |||
CE | Yes |
| Yes | ||
FCC Compliance | CFR 47 Part 15 |
| N/A | ||
Inputs & Outputs (Quantity) |
|
|
|
| |
Digital Inputs (8) | Dry Contact Closure 24VDC, 10 mA | ||||
Analog Inputs (4) | |||||
power source of 12VDC or 24VDC | |||||
| |||||
Digital Outputs (8) | 24VAC, 3A |
| |||
Common Alarm Outputs (2) | 24VAC, 3A |
|
NOTE
If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
83