Default Settings Quick Reference Guide

APPENDIX B - DEFAULT SETTINGS QUICK REFERENCE GUIDE

This appendix provides a quick reference to default settings for the Universal Monitor and the optional Expansion Board. These settings also appear throughout the manual.

Table 37 Universal Monitor - default settings for inputs and outputs

DEFAULT SETTINGS - DIGITAL INPUTS (FROM TABLE 21)

Feature

Default

Other Options

LABEL

INPUT_01 - INPUT_08

Any name (up to eight characters)

NORM OPEN/CLOSE

NO (Normally open)

NC (Normally closed)

ALARM/EVENT

AL (Alarmable)

EV (Event)

LATCHED

NL (Unlatched) / N (No)*

L (Latched) / Y (Yes)*

DELAY

00:01 (1 second)

Any time (in minutes and seconds) from 00:00 to 99:59

*NOTE: Different abbreviations are used to designate a digital input as Latched or Unlatched.

DEFAULT SETTINGS - ANALOG SENSOR INPUTS (FROM TABLE 22)

Feature

Default

Other Options

CONNECTED*

N (Not connected)*

Y (Connected)**

LABEL

SENSOR_1 - SENSOR_4

Any name (up to eight characters)

UNITS

Blank

Any units (up to three characters)

 

 

 

4 mA

-999.9

Can define up to two decimal places—e.g., -99.99

20 mA

+999.9

Can define up to two decimal places—e.g., +99.99

OFFSET

+000.0

Can define up to two decimal places—e.g., +00.00

ALARM/EVENT

AL (Alarmable)

EV (Event)

LATCHED

N (Unlatched)

Y (Latched)

LOW SETPT

-0999.9

Can define up to two decimal places—e.g., -999.99

HIGH SETPT

+0999.9

Can define up to two decimal places—e.g., +999.99

SENSOR DELAY

00:01 (1 second)

Any time (in minutes and seconds) from 00:00 to 99:59

*If a sensor is configured as N (Not connected), the display will show an empty reading (blank spaces). ** If a sensor is configured as Y (Connected) and is functioning properly, the display will show a reading.

If the connected sensor is not functioning properly, the display will show dashes (------) indicating a problem.

DEFAULT MAPPING OF DIGITAL INPUTS TO DIGITAL OUTPUTS (FROM TABLE 23)

Digital input

By default, mapped to digital output:

Input_01

Output01

 

 

 

 

Input_02

Output02

 

 

 

 

Input_03

Output03

 

 

 

 

Input_04

Output04

 

 

 

 

Input_05

Output05

 

 

 

 

Input_06

Output06

 

 

 

 

Input_07

Output07

 

 

 

 

Input_08

Output08

 

 

 

DEFAULT MAPPING OF ANALOG

INPUTS TO DIGITAL OUTPUTS (FROM TABLE 24)

Analog input

By default, mapped to digital output:

Sensor_1

(none)

 

Sensor_2

(none)

 

 

 

 

Sensor_3

(none)

 

 

 

 

Sensor_4

(none)

 

 

 

 

DEFAULT SETTINGS - DIGITAL OUTPUTS (FROM TABLE 25)

 

Feature

Default

Other Options

LABEL

OUTPUT01 - OUTPUT08

Any name (up to eight characters)

NORM OPEN/CLOSE

NO (Normally open)

NC (Normally closed)

132

Page 140
Image 140