Wiring and Connections - Optional Expansion Board
5.0WIRING AND CONNECTIONS - OPTIONAL EXPANSION BOARD
! CAUTION
Remove all power before installing any wiring to the Expansion Board or changing input or output connections.
! WARNING
“RISK OF ELECTRIC SHOCK” - More than one disconnect switch may be required to
5.1Wiring Specifications
Input and output connections to the optional Expansion Board may be made in any
Table 9 | Wiring specifications - optional Expansion Board |
|
|
| ||
|
|
|
|
|
| |
Connection | Supported Wire Type | Maximum Wire Length | Rating | |||
|
|
|
|
|
|
|
Digital |
|
|
|
| Dry Contact | |
| 18 AWG* (recommended) |
|
|
| ||
|
| 750 ft. (225m) |
| (24VDC, | ||
Input |
| Non Plenum - Belden 9740 |
|
| ||
|
|
|
| 10 mA) | ||
|
| Plenum - Belden 89740 |
|
|
| |
|
|
|
|
|
| |
|
|
|
|
|
|
|
|
| 18 AWG* | 20 AWG | 22 AWG |
| |
Digital |
| (recommended) |
| |||
|
|
|
| |||
| 18 AWG* (recommended) |
|
|
| 240VAC, | |
| @3A 50 ft. (15m) | @3A 40 ft. (12m) | @3A 25 ft. (7m) | |||
Output |
| Non Plenum - Belden 9740 | 2A max. | |||
|
| Plenum - Belden 89740 | @2A 100 ft. (30m) | @2A 60 ft. (18m) | @2A 35 ft. (10m) |
|
|
|
| @1A 200 ft. (60m) | @1A 100 ft. (30m) | @1A 75 ft. (23m) |
|
Communication |
|
|
|
| ||
22 AWG* (recommended) |
| 3000 ft. (900m) |
| N/A | ||
EIA485 |
| Non Plenum - Belden 9461 |
|
| ||
|
|
|
|
| ||
|
| Plenum - Belden 88761 |
|
|
|
|
|
|
|
|
|
|
|
24VAC Power |
|
|
|
| ||
18 AWG* (recommended) |
|
|
| 24VAC | ||
Connection |
| 150 ft. (45m) |
| |||
Non Plenum - Belden 8770 |
|
| @0.6A | |||
(TB1) |
|
|
|
| ||
| Plenum - Belden 88770 |
|
|
|
| |
|
|
|
|
|
| |
|
|
|
|
|
| |
* Recommended |
|
|
|
|
|
25