System and Control Options

9.11Manual Output Ctrl

The Manual Output Ctrl feature allows you to manually change the state of any digital output to ON or OFF, overriding automatic control by the Universal Monitor (the default setting for all outputs). This menu also allows you to release the manual override, returning any output to automatic control.

There are two ways to override automatic control of outputs:

Use the Manual Output Ctrl menu, as described in this section, to turn any output ON or OFF.

Use the switch on the Universal Monitor board (see 1.7 - Controller Board Overview) to force all eight outputs ON at the same time. (Note: This has no effect on the optional Expansion Board outputs.)

After an output is forced manually ON or OFF through the Manual Output Ctrl menu, it remains in that state until returned to automatic control through this menu.

Table 34 summarizes the four types of control, including the abbreviated message that appears on the LCD and in log reports.

Table 34 Automatic / manual control - output points

Message

 

Description

 

 

 

AUTO

Automatic

Controlled by Universal Monitor

 

 

 

MAN ON

Manually ON

This output forced ON or OFF

MAN OFF

Manually OFF

via Manual Output Ctrl menu

 

 

 

HW MAN ON

Manually ON

All outputs forced ON

(all outputs)

via hardware switch on circuit board

 

To force an output point ON or OFF or return it to automatic control:

Log In and Choose Manual Output Ctrl

From the Main Menu, use the arrows ↑ ↓ to choose System and Control, then press Enter (see 9.1 - Login for help).

Enter your password at the Login screen.

From the System and Control Menu, use the arrows ↑ ↓to choose Manual Output Ctrl, then press Enter .

Select an Output

The Select Output menu, shown at right, display the current status of all eight outputs.

Use the arrows ↑ ↓ to choose the output you want—for example, Output01—and press Enter .

Turn Output ON or OFF / Return to Automatic

From the Override Output menu, use the arrows ↑ ↓ to choose one of these options:

Auto (return to automatic control)

Man ON (manually turn this output ON)

Man OFF (manually turn this output OFF)

Press Enter .

Main Menu

VIEW STATUS

> SYSTEM AND CONTROL

↑ ↓=NEXT

=SELECT

Login

LOGIN

AAAA

=SELECT =NEXT/END

System & Control Menu

SETUP SYSTEM

>MANUAL OUTPUT CTRL

CLEAR ALARMS & LOGS ↑ ↓=NEXT =SELECT

Select Output

OVERRIDE OUTPUT

>OUTPUT01 AUTO

OUTPUT02 AUTO

↑ ↓=NEXT =SELECT

OUTPUT03 AUTO OUTPUT04 MAN ON OUTPUT05 AUTO OUTPUT06 AUTO OUTPUT07 MAN OFF OUTPUT08 AUTO OUTPUT09 AUTO OUTPUT10 MAN ON OUTPUT11 AUTO OUTPUT12 AUTO OUTPUT13 MAN OFF OUTPUT14 AUTO OUTPUT15 AUTO OUTPUT16 AUTO

Override Output

SELECT OUTPUT01

AUTO

↑ ↓=SELECT =END

NOTE: OUTPUT09-OUTPUT16 for optional Expansion Board