System and Control Options

9.7Setup System - Setup Output

The Universal Monitor has eight outputs that may be configured indi- vidually. If the optional Expansion Board is used, its additional eight digital outputs may be renamed. The outputs may have a wide variety of Liebert or other manufacturers’ equipment connected for configured responses to input alarms and events.

To configure an output:

Log In and Choose Setup System

From the Main Menu, use the arrows ↑ ↓ to choose System and Control, then press Enter (see 9.1 - Login for help).

Enter your password at the Login screen.

From the System and Control Menu, use the arrows ↑ ↓ to choose Setup System, then press Enter .

Select an Output to Configure

From the Setup System Menu, shown at right, use the arrows ↑ ↓ to choose Setup Output and press Enter .

From the Select Output Menu, choose the output you want—for example, Output01—and press Enter .

Table 25 shows digital output features and default settings. You may change the name of any output. In addition, the Universal Monitor’s eight outputs may be defined as normally open or closed.

Use the steps following Table 25 to change the default settings for any digital output.

Table 25 Default settings - digital outputs

Feature

Default

Other Options

 

 

 

LABEL

OUTPUT01

Any name (up to eight

characters)

 

 

NORM OPEN/CLOSE

NO (Normally open)

NC (Normally closed)

(Main board only)

 

 

9.7.1Change Label (Name of Output)

Each output has a default label (Output01, Output02, etc.) that you may change to a more descriptive name. The label may consist of up to eight characters (see Table 20 for valid characters).

From the Setup Output Menu, as shown at right, use the arrows ↑ ↓ to choose Change Label for the selected output and press Enter .

To change the output’s label, which may consist of up to eight char- acters:

Use the arrows ↑ ↓ to choose a character.

Press Enter to advance to the next character position.

When finished, press Enter again.

9.7.2Define Main Board Output as Normally Open / Closed

Each output may be set up as Normally Open (NO) or Normally Closed (NC). The default setting for all output points is NO (Normally Open).

From the Setup Output Menu, choose Change State, as shown at right, and press Enter .

To change the normal state for this output, use the arrows ↑ ↓ to choose NO (Normally Open) or NC (Normally Closed), then press Enter .

Setup System Menu

SETUP INPUT

SETUP COMMON ALARM

SETUP SENSOR

SETUP I/O MATRIX

↑ ↓=NEXT =SELECT

>SETUP OUTPUT SETUP MODEM&PAGERS SETUP SYSTEM INFO SETUP EXP BOARD

Select Output Menu

SELECT OUTPUT

 

> OUTPUT01

NO

 

 

 

 

OUTPUT02

NO

 

 

 

 

↑ ↓=NEXT

=SELECT

 

 

 

 

 

 

 

 

 

 

 

 

OUTPUT03

NO

 

 

 

 

OUTPUT04

NO

 

 

 

 

OUTPUT05

NO

 

 

 

 

OUTPUT06

NO

 

 

 

 

OUTPUT07

NO

 

 

 

 

OUTPUT08

NO

 

 

 

 

OUTPUT09

NO

 

 

 

 

OUTPUT10

NO

 

 

 

 

OUTPUT11

NO

 

 

 

 

OUTPUT12

NO

 

 

 

 

OUTPUT13

NO

 

 

 

 

OUTPUT14

NO

 

 

 

 

OUTPUT15

NO

 

 

 

 

OUTPUT16

NO

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE: OUTPUT09-OUTPUT16 for optional Expansion Board

Setup Output Menu

>CHANGE LABEL CHANGE STATE

↑ ↓=NEXT =SELECT

Change Label

CHANGE LABEL

LABEL: OUTPUT01

=SELECT =NEXT/END

Setup Output Menu

CHANGE LABEL

> CHANGE STATE

↑ ↓=NEXT =SELECT

Change State

SET TO NORMAL OPEN OR NORMAL CLOSE? NO

↑ ↓=NO/NC

=END

58

Page 66
Image 66
Liebert Universal Monitor user manual Setup System Setup Output, Change Label Name of Output