Wiring and Connections - Main Board

4.0WIRING AND CONNECTIONS - MAIN BOARD

! CAUTION

Switch OFF electric power to the Universal Monitor before installing any wiring to the unit or changing input or output connections. The Power On/Off switch is in the top left corner of the unit, just below the battery pack.

4.1Wiring Specifications

Input and output connections to the Universal Monitor may be made in any order—it is not neces- sary, for example, to make all input connections before making any output connections. Use copper conductors only for all wiring.

Table 7

Wiring specifications - main board

 

 

 

 

 

 

 

 

 

Connection

Supported Wire Type

Maximum Wire Length

Rating

 

 

 

 

 

 

 

Digital

 

18-22 AWG Stranded & Unshielded

 

 

 

Dry Contact

 

18 AWG* (recommended)

 

 

 

 

 

750 ft. (225m)

 

(24VDC,

Input

 

Non Plenum - Belden 9740

 

 

 

 

 

 

10 mA)

 

 

Plenum - Belden 89740

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18-22 AWG Stranded & Unshielded

18 AWG*

20 AWG

22 AWG

 

Digital

 

(recommended)

 

 

18 AWG* (recommended)

 

 

 

24VAC

 

@3A 50 ft. (15m)

@3A 40 ft. (12m)

@3A 25 ft. (7m)

Output

 

Non Plenum - Belden 9740

@3A

 

 

Plenum - Belden 89740

@2A 100 ft. (30m)

@2A 60 ft. (18m)

@2A 35 ft. (10m)

 

 

 

 

@1A 200 ft. (60m)

@1A 100 ft. (30m)

@1A 75 ft. (23m)

 

Analog Input

18-22 AWG Stranded & Unshielded

 

 

 

4-20 mA Signal

18 AWG* (recommended)

 

 

 

Input Selectable

2-Wire

 

 

750 ft. (225m)

 

 

Non Plenum - Belden 9740

 

 

Power Source

Transducer

 

 

 

Plenum - Belden 89740

 

 

 

(12/24VDC)

 

 

 

 

 

 

 

 

 

 

 

 

Analog Input

18-22 AWG Stranded & Unshielded

 

 

 

4-20 mA Signal

18 AWG* (recommended)

 

 

 

Input Selectable

4-Wire

 

 

750 ft. (225m)

 

 

Non Plenum - Belden 8489

 

 

Power Source

Transducer

 

 

 

Plenum - Belden 88489

 

 

 

(12/24VDC)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18-22 AWG Stranded & Unshielded

18 AWG*

20 AWG

22 AWG

 

Common

(recommended)

 

 

 

 

Alarm

 

18 AWG* (recommended)

 

 

 

24VAC

 

@3A 50 ft. (15m)

@3A 40 ft. (12m)

@3A 25 ft. (7m)

 

Non Plenum - Belden 9740

@3A

Output

 

Plenum - Belden 89740

@2A 100 ft. (30m)

@2A 60 ft. (18m)

@2A 35 ft. (10m)

 

 

 

 

@1A 200 ft. (60m)

@1A 100 ft. (30m)

@1A 75 ft. (23m)

 

Communication

Null Modem Cable

 

50 ft. (15m)

 

N/A

RS232

 

 

 

 

 

 

Communication

18-22 AWG Stranded & Shielded

 

 

 

 

EIA422

 

22 AWG* (recommended)

 

1000 ft. (300m)

 

N/A

 

Non Plenum - Belden 9461

 

 

SiteScan

 

 

 

 

Plenum - Belden 88761

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Communication

18-22 AWG Stranded & Shielded

 

 

 

 

22 AWG* (recommended)

 

3000 ft. (900m)

 

N/A

EIA485

 

Non Plenum - Belden 9461

 

 

 

 

 

 

 

 

 

Plenum - Belden 88761

 

 

 

 

 

 

 

 

 

 

Phone/Modem

4 Wire (Pins 3 & 4)

 

N/A

 

N/A

Line

 

RJ11 Connector

 

 

 

 

 

 

 

24VAC Power

18-22 AWG Stranded & Shielded

 

 

 

 

18 AWG* (recommended)

 

 

 

24VAC

Connection

 

150 ft. (45m)

 

Non Plenum - Belden 8770

 

 

@1.3A

(TB7)

 

 

 

 

 

Plenum - Belden 88770

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power Connections (Transformer Module)

 

 

 

 

115VAC

 

14 AWG Stranded & Unshielded

 

150 ft. (45m)

 

115VAC

 

Non Plenum - Belden 5101UE

 

 

@4A

 

 

 

 

 

230VAC

 

14 AWG Stranded & Unshielded

 

150 ft. (45m)

 

230VAC

 

Non Plenum - Belden 5101UE

 

 

@0.5A

 

 

 

 

 

* Recommended

20

Page 28
Image 28
Liebert Universal Monitor Wiring Specifications, Wiring and Connections Main Board, Wiring specifications main board