System and Control Options
9.5.9Change Low Setpoint
The Low Setpoint value is typically above the 4 mA value for the sen- sor. For example, if the 4 mA value is 50°F, the Low Setpoint might be 60°F. When the sensor crosses below this value, an alarm or event will occur, depending on the sensor configuration.
The default Low Setpoint for each sensor is
•the 4 mA value + the Offset value (in the example, 50+5=55) to
•the 20 mA value + the Offset value (in the example, 90+5=95)
To determine these values, see 9.5.4 - Change 4 mA Value, 9.5.5 - Change 20 mA Value and 9.5.6 - Change Offset Value.
To enter a new value:
•From the Setup Sensor Menu, choose Low Setpt for the selected sensor and press Enter ↵ .
•To change the Low Setpoint:
•Use the arrows ↑ ↓ to choose a character.
•Press Enter ↵ to advance to the next character position.
•When finished, press Enter ↵ again.
Setup Sensor Menu
SETUP SENSOR_1 CONNECTED : Y LABEL: ROOM_TMP
↑↓=NEXT ↵ =SELECT
UNITS: DEG
4 mA: +050.0
20 mA: +090.0
OFFSET: +005.0
ALARM/EVENT: AL
LATCHED: N
>LOW SETPT: +0055.0
HIGH SETPT: +0999.9
SENSOR DELAY: 00:01
Change Low Setpoint
CHANGE LOW SETPOINT
LOW SETPT: +0060.0
↑↓=SELECT ↵ =NEXT/END
9.5.10Change High Setpoint
The High Setpoint value is typically below the 20 mA value for the sen- sor. For example, if the 20 mA value is 90°F, the High Setpoint might be 85°F. When the sensor crosses above this value, an alarm or event will occur, depending on the sensor configuration.
The default High Setpoint for each sensor is +950.0. Values that can be entered range from:
•the 4 mA value + the Offset value (in the example, 50+5=55) to
•the 20 mA value + the Offset value (in the example, 90+5=95)
To determine these values, see 9.5.4 - Change 4 mA Value, 9.5.5 - Change 20 mA Value and 9.5.6 - Change Offset Value.
To enter a new value:
•From the Setup Sensor Menu, choose High Setpt for the selected sensor and press Enter ↵ .
•To change the High Setpoint:
•Use the arrows ↑ ↓ to choose a character.
•Press Enter ↵ to advance to the next character position.
•When finished, press Enter ↵ again.
Setup Sensor Menu
SETUP SENSOR_1 CONNECTED : Y LABEL: ROOM_TMP
↑↓=NEXT ↵ =SELECT
UNITS: DEG
4 mA: +050.0
20 mA: +090.0
OFFSET: +005.0
ALARM/EVENT: AL
LATCHED: N
LOW SETPT: +0060.0
>HIGH SETPT: +0095.0
SENSOR DELAY: 00:01
Change High Setpoint
CHANGE HIGH SETPOINT
HIGH SETPT: +0085.0
↑↓=SELECT ↵ =NEXT/END
53