System and Control Options

9.5.9Change Low Setpoint

The Low Setpoint value is typically above the 4 mA value for the sen- sor. For example, if the 4 mA value is 50°F, the Low Setpoint might be 60°F. When the sensor crosses below this value, an alarm or event will occur, depending on the sensor configuration.

The default Low Setpoint for each sensor is -950.0. Values that can be entered range from:

the 4 mA value + the Offset value (in the example, 50+5=55) to

the 20 mA value + the Offset value (in the example, 90+5=95)

To determine these values, see 9.5.4 - Change 4 mA Value, 9.5.5 - Change 20 mA Value and 9.5.6 - Change Offset Value.

To enter a new value:

From the Setup Sensor Menu, choose Low Setpt for the selected sensor and press Enter .

To change the Low Setpoint:

Use the arrows ↑ ↓ to choose a character.

Press Enter to advance to the next character position.

When finished, press Enter again.

Setup Sensor Menu

SETUP SENSOR_1 CONNECTED : Y LABEL: ROOM_TMP

=NEXT =SELECT

UNITS: DEG

4 mA: +050.0

20 mA: +090.0

OFFSET: +005.0

ALARM/EVENT: AL

LATCHED: N

>LOW SETPT: +0055.0

HIGH SETPT: +0999.9

SENSOR DELAY: 00:01

Change Low Setpoint

CHANGE LOW SETPOINT

LOW SETPT: +0060.0

=SELECT =NEXT/END

9.5.10Change High Setpoint

The High Setpoint value is typically below the 20 mA value for the sen- sor. For example, if the 20 mA value is 90°F, the High Setpoint might be 85°F. When the sensor crosses above this value, an alarm or event will occur, depending on the sensor configuration.

The default High Setpoint for each sensor is +950.0. Values that can be entered range from:

the 4 mA value + the Offset value (in the example, 50+5=55) to

the 20 mA value + the Offset value (in the example, 90+5=95)

To determine these values, see 9.5.4 - Change 4 mA Value, 9.5.5 - Change 20 mA Value and 9.5.6 - Change Offset Value.

To enter a new value:

From the Setup Sensor Menu, choose High Setpt for the selected sensor and press Enter .

To change the High Setpoint:

Use the arrows ↑ ↓ to choose a character.

Press Enter to advance to the next character position.

When finished, press Enter again.

Setup Sensor Menu

SETUP SENSOR_1 CONNECTED : Y LABEL: ROOM_TMP

=NEXT =SELECT

UNITS: DEG

4 mA: +050.0

20 mA: +090.0

OFFSET: +005.0

ALARM/EVENT: AL

LATCHED: N

LOW SETPT: +0060.0

>HIGH SETPT: +0095.0

SENSOR DELAY: 00:01

Change High Setpoint

CHANGE HIGH SETPOINT

HIGH SETPT: +0085.0

=SELECT =NEXT/END

53

Page 61
Image 61
Liebert Universal Monitor user manual Change Low Setpoint, Change High Setpoint