System and Control Options

9.5.4Change 4 mA Value

For the 4 mA value, enter the smallest value for the range of the sen- sor—for example, 50°F for a temperature sensor with a range of 50°F to 90°F.

The default value for each sensor is -999.9. Values that can be entered range from -999.9 to +999.9.

To enter a new value:

•From the Setup Sensor Menu, choose 4 mA for the selected sensor and press Enter ↵ .

•To change the 4 mA value:

•Use the arrows ↑ ↓ to choose a character.

•Press Enter ↵ to advance to the next character position.

•When finished, press Enter ↵ again.

9.5.5Change 20 mA Value

For the 20 mA value, enter the largest value for the range of the sen- sor—for example, 90°F for a temperature sensor with a range of 50°F to 90°F.

The default value for each sensor is +999.9. Values that can be entered range from -999.9 to +999.9.

To enter a new value:

•From the Setup Sensor Menu, choose 20 mA for the selected sen- sor and press Enter ↵ .

•To change the 20 mA value:

•Use the arrows ↑ ↓ to choose a character.

•Press Enter ↵ to advance to the next character position.

•When finished, press Enter ↵ again.

9.5.6Change Offset Value

For the Offset value, enter an adjustment factor—for example, if the sensor reading shows 70°F when the actual temperature is 75°F, the offset might be 5°F.

The default Offset value for each sensor is +000.0. Values that can be entered range from -999.9 to +999.9.

To enter a new value:

•From the Setup Sensor Menu, choose Offset for the selected sensor and press Enter ↵ .

•To change the Offset value:

•Use the arrows ↑ ↓ to choose a character.

•Press Enter ↵ to advance to the next character position.

•When finished, press Enter ↵ again.

Setup Sensor Menu

SETUP SENSOR_1 CONNECTED : Y LABEL: ROOM_TMP

↑↓=NEXT ↵ =SELECT

UNITS: DEG

>4 mA: -999.9

20 mA: +999.9

OFFSET: +000.0

ALARM/EVENT: AL

LATCHED: N

LOW SETPT: -0999.9

HIGH SETPT: +0999.9

SENSOR DELAY: 00:01

Change 4 mA Value

CHANGE 4 mA VALUE

4 mA: +050.0

↑↓=SELECT ↵ =NEXT/END

Setup Sensor Menu

SETUP SENSOR_1 CONNECTED : Y LABEL: ROOM_TMP

↑↓=NEXT ↵ =SELECT

UNITS: DEG

4 mA: +050.0

>20 mA: +999.9

OFFSET: +000.0

ALARM/EVENT: AL

LATCHED: N

LOW SETPT: -0999.9

HIGH SETPT: +0999.9

SENSOR DELAY: 00:01

Change 20 mA Value

CHANGE 20 mA VALUE

20 mA: +090.0

↑↓=SELECT ↵ =NEXT/END

Setup Sensor Menu

SETUP SENSOR_1 CONNECTED : Y LABEL: ROOM_TMP

↑↓=NEXT ↵ =SELECT

UNITS: DEG

4 mA: +050.0

20 mA: +090.0

>OFFSET: +000.0

ALARM/EVENT: AL

LATCHED: N

LOW SETPT: -0999.9

HIGH SETPT: +0999.9

SENSOR DELAY: 00:01

Change Offset Value

CHANGE OFFSET VALUE

OFFSET: +005.0

↑↓=SELECT ↵ =NEXT/END

51

Page 59
Image 59
Liebert Universal Monitor user manual Change 4 mA Value, Change 20 mA Value, Change Offset Value