System and Control Options
9.5.11Set Up Delay Time
Each sensor may be set up with a specified time delay between the triggering of a high or low
This delay is the amount of time that must elapse before the Universal Monitor acknowledges the change in the monitored sensor and takes any further action, such as dialing configured pagers. The default time delay is 1 second (displayed as 00 MIN : 01 SEC).
The time delay applies to the triggering of a high or low setpoint and also after the monitored sensor returns to its normal state. When the monitored device returns to its normal state, the specified time delay must elapse before the Universal Monitor acknowledges the
•From the Setup Sensor Menu, choose Sensor Delay, as shown at right, and press Enter ↵ .
•To change the time delay in minutes and seconds (in the range of 00:00 to 99:59):
Setup Sensor Menu
SETUP SENSOR_1 CONNECTED : Y LABEL: ROOM_TMP
↑↓=NEXT ↵ =SELECT
UNITS: DEG
4 mA: +050.0
20 mA: +090.0
OFFSET: +005.0
ALARM/EVENT: AL
LATCHED: N
LOW SETPT: +055.00
HIGH SETPT: +085.00
SENSOR DELAY: 00:01
Delay Time
DELAY TIME BEFORE TRIGGER?
00 MIN : 01 SEC
↑↓=SELECT ↵ =NEXT/END
•For minutes (MIN), press and hold one of the arrow keys ↑ ↓ scroll through the numbers
•Press Enter ↵ to advance to seconds (SEC).
•For seconds (SEC), press and hold one of the arrow keys ↑ ↓ scroll through the numbers
54