Chapter 2. Installation

AC Powered Unit

The AC powered ATLAS 810PLUS (P/N 1200265L1) comes equipped with a detachable 8-foot power cord with a 3-prong plug for connecting to a grounded power receptacle.

Power to the ATLAS 810PLUS must be from a grounded 115 VAC, 60 Hz or 220 VAC, 50-60 Hz source.

DC Powered Unit

The DC powered ATLAS 810PLUS (P/N 1200266L1) comes equipped with a terminal block on the rear of the unit. The power source should be connected to the terminal block according to the polarity markings on the unit. For ex- ample, a -48 V source would be connected with the -48 V return connected to the (+) terminal and the -48 VDC attached to the (-) terminal. Power must be from a DC power source in the range of 42 to 57 VDC, capable of deliver- ing up to 7 A of current.

The

This unit shall be installed in accordance with Article 400 and 364.8 of the NEC NFPA 70 when installed outside of a Restricted Access Location (i.e., central office, behind a locked door, service personnel only area).

• The branch circuit overcurrent protection shall be a fuse or circuit breaker rated minimum 48 V, maximum 20 A.

A readily accessible disconnect device that is suitably approved and rated shall be incorporated into the fixed wiring.

GROUNDING INSTRUCTIONS

This section provides grounding instruction information from the Under- writers' Laboratory UL 1950 Standard for Safety of Information Technology Equipment Including Electrical Business Equipment, of July 28, 1995.

An equipment grounding conductor that is not smaller in size than the un- grounded branch-circuit supply conductors is to be installed as part of the circuit that supplies the product or system. Bare, covered, or insulated grounding conductors are acceptable. Individually covered or insulated equipment grounding conductors shall have a continuous outer finish that is either green, or green with one or more yellow stripes. The equipment grounding conductor is to be connected to ground at the service equipment.

The attachment-plug receptacles in the vicinity of the product or system are all to be of a grounding type, and the equipment grounding conductors serv- ing these receptacles are to be connected to earth ground at the service equipment.

2-2

ATLAS 810PLUS User Manual

61200266L1-1