Reference Manual
Rosemount 8732
FOXBORO SENSORS
Series 1800 Sensor to Rosemount 8732 Transmitter
Connect coil drive and electrode cables as shown in Figure
Figure E-12. Wiring Diagram for
Foxboro Series 1800 and
Rosemount 8732
FOXBORO SERIES | ROSEMOUNT 8732 |
1800 SENSOR | TRANSMITTER |
Electrode Connections |
|
Outer Shield |
|
White Lead |
|
White Shield |
|
Black Lead |
|
Black Shield |
|
Inner Shield |
|
Coil Connections |
|
Table E-13. Foxboro Generic Sensor Wiring Connections
Rosemount 8732 |
| Foxboro Series 1800 Sensors | ||||
1 |
|
|
| L1 | ||
2 |
|
|
| L2 | ||
|
|
|
|
|
| Chassis Ground |
|
|
|
|
| ||
17 |
|
| Any Shield | |||
18 |
|
| Black | |||
19 |
|
| White | |||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
This is a pulsed DC magnetic flowmeter.
Do not connect AC power to the sensor or to terminals 1 and 2 of the transmitter, or replacement of the electronics board will be necessary.