Low Flow Cutoff

E-SERIES ADVANCED DIAGNOSTICS CAPABILITIES

Adjustable between 0.01 and 38.37 ft./s (0.003 and 11.7 m/s). Below selected value, output is driven to the zero flow rate signal level.

Overrange Capability

Signal output will remain linear until 110% of upper range value or 44 ft./s (13 m/s). The signal output will remain constant above these values. Out of range message displayed on LOI and the Field Communicator.

Damping

Adjustable between 0 and 256 seconds

Basic

Self test

Transmitter faults

Analog output test

Pulse output test

Tunable empty pipe

Reverse flow

Coil circuit fault

Electronics temperature

Process Diagnostics (D01)

Ground/wiring fault

High process noise

SMART Meter Verification (D02)

Smart Meter Verification

OUTPUT SIGNALS

8732 LOI Lockout

PROFIBUS PA FIELDBUS DIGITAL OUTPUT SPECIFICATIONS

All optical switches on the display can be locked locally from the display layout configuration screen by holding the upper right optical switch for 10 seconds. The display can be reactivated holding the same switch for 10 seconds.

Output Signal

Manchester-encoded digital signal that conforms to IEC 1158-2 and ISA 50.02.

Profile Version

3.01

Identification Number

Generic: 0x9740

Manufacturer Specific: 0x0C15

A-4

Page 78
Image 78