Rosemount 8732
Reference Manual
| Profibus PA specific |
|
| Parameters |
|
26 | TOTAL | The Function Block parameter TOTAL contains |
|
| the integrated quantity of the rate parameter |
|
| provided by CHANNEL and the associated |
|
| status. |
27 | UNIT_TOT | Unit of the totalized quantity. |
28 | CHANNEL | Reference to the active Transducer Block, |
|
| which provides the measurement value to the |
|
| Function Block. |
29 | SET_TOT | The following selections of this Function Block |
|
| parameter are possible: |
|
| 0: TOTALIZE; “normal“ operation of the Totalizer |
|
| 1: RESET; assign value “0“ to Totalizer |
|
| 2: PRESET; assign value of PRESET_TOT to |
|
| Totalizer |
30 | MODE_TOT | 0: BALANCED; true arithmetic integration of the |
|
| incoming rate values. |
|
| 1: POS_ONLY; totalization of positive incoming |
|
| rate values only. |
|
| 2: NEG_ONLY; totalization of negative incoming |
|
| rate values only. |
|
| 3: HOLD; totalization stopped |
31 | FAIL_TOT | 0: RUN; totalization is continued using the input |
|
| values despite the BAD status. |
|
| The status is ignored. |
|
| 1: HOLD; totalization is stopped during |
|
| occurrence of BAD status of incoming |
|
| values. |
|
| 2: MEMORY; totalization is continued based on |
|
| the last incoming value |
|
| with GOOD status before the first occurrence of |
|
| BAD status. |
32 | PRESET_TOT | This value is used as a preset for the internal |
|
| value of the FB algorithm. The value is effective |
|
| if using the SET_TOT function. |
33 | ALARM_HYS | Within the scope of the |
|
| specification for transmitters there are |
|
| functions for the monitoring of limit violation |
|
| |
|
| Maybe the value of one process variable is just |
|
| the same as the value of a limit and the variable |
|
| fluctuates around the limit it will occur a lot of |
|
| limit violations. That triggers a lot of messages; |
|
| so it must be possible to trigger messages only |
|
| after crossing an adjustable hysteresis. The |
|
| sensitivity of triggering of the alarm messages is |
|
| adjustable. The value of the hysteresis is fixed |
|
| in ALARM_HYS and is the same for the |
|
| parameters HI_HI_LIM, HI_LIM, LO_LIM and |
|
| LO_LO_LIM. The hysteresis is expressed as |
|
| value below high limit and above low limit in the |
|
| engineering unit of xx_LIM. |
34 | HI_HI_LIM | Value for upper limit of alarms |
35 | HI_LIM | Value for upper limit of warnings |
36 | LO_LIM | Value for lower limit of warnings |
37 | LO_LO_LIM | Value for the lower limit of alarms |
38 - 51 | RESERVED BY PNO |
|
52 | VIEW_1_TOT |
|
|
|
|