Reference Manual

00809-0100-4665, Rev AA August 2010

Rosemount 8732

Class 2 Masters

There are a number of available PROFIBUS configuration tools. These Class 2 Masters are manufacturer-independent tools for the operation, configuration, maintenance, and diagnosis of intelligent field devices. Device descriptor based Class 2 Masters allow 100% configuration capability on the 8732E Profibus PA transmitter.

Class 2 Masters always need to be connected to the DP segment. They cannot be directly connected to a PA segment.

DIAGNOSTICS

Diagnostics are used to verify that the transmitter is functioning properly, to

 

assist in troubleshooting, to identify potential causes of error messages, and

 

to verify the health of the transmitter and sensor. All the diagnostic test can be

 

initiated through the use of a Class 2 Master. Some diagnostics can be

 

accessed using the LOI.

 

Rosemount offers several different diagnostic suites providing various

 

functionality.

 

Standard diagnostics included with every Rosemount 8732 transmitter are

 

Empty Pipe detection, Electronics Temperature monitoring, Coil Fault

 

detection, and various loop and transmitter tests.

 

Advanced diagnostics suite option one (D01 option) contains advanced

 

diagnostics for High Process Noise detection and Grounding and Wiring fault

 

detection.

 

Advanced diagnostics suite option two (D02 option) contains advanced

 

diagnostics for the 8714i Meter Verification. This diagnostic is used to verify

 

the accuracy and performance of the magnetic flow meter installation.

 

Empty Pipe Detection

 

Turn the empty pipe diagnostic on or off as required by the application. For

 

more details on the empty pipe diagnostic, see Appendix C: Diagnostics.

 

Electronics Temperature Out of Range

 

Turn the electronics temperature diagnostic on or off as required by the

 

application. For more details on the electronics temperature diagnostic, see

 

Appendix C: Diagnostics.

 

High Process Noise Detection

 

Turn the high process noise diagnostic on or off as required by the

 

application. For more details on the high process noise diagnostic, see

 

Appendix C: Diagnostics.

 

Grounding / Wiring Fault Detection

 

Turn the grounding / wiring diagnostic on or off as required by the application.

 

For more details on the grounding / wiring diagnostic, see Appendix C:

 

Diagnostics.

4-3

Page 33